![Mitsubishi FR-A846-00023 Instruction Manual Download Page 9](http://html1.mh-extra.com/html/mitsubishi/fr-a846-00023/fr-a846-00023_instruction-manual_1809256009.webp)
Product checking and accessories
8
1.1
Product checking and accessories
Unpack the product and check the rating plate and the capacity plate of the inverter to ensure that the model agrees with the
order and the product is intact.
Inverter model
Specification differs by the type. Major differences are shown in the table below.
NOTE
• Hereinafter, the inverter model name consists of the applicable motor capacity and the rated current value (SLD rated current
value of the A800 standard model).
(Example) FR-A846-00250(7.5K)
How to read the SERIAL number
Type
Monitor output
Initial setting
Built-in EMC filter
Control
logic
Rated
frequency
Pr.19 Base
frequency voltage
FM
(terminal FM
equipped model)
Terminal FM (pulse train output)
Terminal AM (analog voltage output
(0 to ±10 VDC))
Built-in C2 filter: ON,
Built-in C3 filter: OFF
Sink logic
60 Hz
9999 (same as the
power supply voltage)
CA
(terminal CA
equipped model)
Terminal CA (analog current output
(0 to 20 mADC))
Terminal AM (analog voltage output
(0 to ±10 VDC))
ON
Source logic 50 Hz
8888 (95% of the
power supply voltage)
Rating plate example
The SERIAL consists of one symbol, two characters indicating the production
year and month, and six characters indicating the control number. The last digit
of the production year is indicated as the Year, and the Month is indicated by 1
to 9, X (October), Y (November), or Z (December).
Symbol Year
Month
Control number
SERIAL
Rating plate
Input rating
Output rating
SERIAL
Inverter model
F R - A 8 4 6 - 00250 -1 -60 C3
400 V class
Symbol
Voltage class
4
CA
Symbol
Type
∗1
FM
-2
-1
Symbol
Description
0.4K to 132K
Inverter ND rated capacity (kW)
00023 to 03610
Inverter rated current
(SLD rated current of the
A800 standard model) (A)
Symbol
Structure, functionality
IP55 compatible model
6
Built-in C3 filter
C3
C2
EMC filter
Symbol
Built-in C2 filter
Symbol
Circuit board coating
(conforming to IEC60721-3-3 3C2/3S2)
With
With
Plated conductor
With
Without
-06
-60
Country of origin