73
DETAILS OF INPUT AND
OUTPUT SIGNALS
7
7.2.4 Monitor codes
Monitor items selected with RWw0, RWw4 to 7 are explained below.
Devide the monitor code (RWw0) into half to select the first monitor description (RWr0) from the lower 8
bits and the second monitor description (RWr1) from the upper 8 bits.
(Example) When output current is selected for the first monitor and running speed is selected for the
second monitor
→
monitor code is H0602
REMARKS
When
Pr. 544
= 12, 14, 18, (114, 118) descriptions of monitor code 3 (RWw4) to 6 (RWw7) can be selected.
Code
Number
Second Monitor Description
(the first 8 bits)
First, Third to Sixth Monitor Description
(the last 8 bits)
Increments
H00
Output frequency
No monitoring (monitor value is 0)
0.01Hz
H01
Output frequency
0.01Hz
H02
Output current
0.01A / 0.1A
H03
Output voltage
0.1V
H05
Set frequency
0.01Hz
H06
Running speed
1r/min / 0.1r/min
H07
Motor torque
0.1%
H08
Converter output voltage
0.1V
H09
Regenerative brake duty
0.1%
H0A
Electronic thermal relay function load factor
0.1%
H0B
Output current peak
0.01A / 0.1A
H0C
Converter output voltage peak
0.1V
H0D
Input power
0.01kW / 0.1kW
H0E
Output power
0.01kW / 0.1kW
H0F
Input terminal status
H10
Output terminal status
H11
Load meter
0.1%