16
- 16 -
HWE10170
GB
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to
compressor inverter on fan inverter.
Example
Code 4225 (detail code 108): Bus voltage drop in the fan inverter system
Code 4230 : Heatsink overheat protection in the compressor inverter system
There are no preliminary error codes or detail codes for indoor units.
XII
6608
-
-
No response error
O
O
O
O
6831
-
-
MA controller signal reception error (No signal re-
ception)
O
O
6832
-
-
MA remote controller signal transmission error
(Synchronization error)
O
O
6833
-
-
MA remote controller signal transmission error
(Hardware error)
O
O
6834
-
-
MA controller signal reception error (Start bit de-
tection error)
O
O
7100
-
-
Total capacity error
O
7101
-
-
Capacity code setting error
O
O
O
7102
-
-
Wrong number of connected units
O
7105
-
-
Address setting error
O
7106
-
-
Attribute setting error
O
7110
-
-
Connection information signal transmission/recep-
tion error
O
7111
-
-
Remote controller sensor fault
O
O
7113
-
-
Function setting error
O
7117
-
-
Model setting error
O
7130
-
-
Incompatible unit combination
O
The last digit
Inverter system
0 or 1
Compressor inverter system
5
Fan inverter system
Error
Code
Prelimi-
nary
error
code
Error
(prelim-
inary)
detail
code
Error code definition
Searched unit
Notes
Outdoor unit
Indoor unit
LOSSNAY
Remote controller
HWE10170.book 16 ページ 2011年7月19日 火曜日 午後2時57分