8
-
23
(10)I/O assignment
The mounting status of each module in the system is set.
(To the next page)
Figure 8.21 I/O assignment
Table8.21 I/O assignment setting list
Item
Parameter
No.
Description
Setting range
Default
Reference
I/O
Assignme
nt
Type
0400
H
Set the type of the mounted module.
• CPU No.2 to No.4: No.n/Empty (Set
"CPU (Empty)" for the slot where no
CPU module is mounted.)
• Empty, Input, Hi input, Output,
Intelli., I/O mix, or Interrupt
Blank
Model name
Set the model name of the mounted
module. (Entered at user's discretion.
Do not use the one for the CPU
module.)
Up to 16 characters
Points
Set the number of points assigned to
each slot.
0, 16, 32, 48, 64, 128, 256, 512, or
1024 points
Start XY
Set the start I/O number of each slot.
0
H
to FF0
H
Base
setting
Base model
name
0401
H
Set the model name of the main base
unit or extension base unit. (Entered
at user's discretion. Do not use the
one for the CPU module.)
Up to 16 characters
Blank
Power model
name
Set the model name of the power
supply module on the main base unit
or extension base unit. (Entered at
user's discretion. Do not use the one
for the CPU module.)
Up to 16 characters
Extension
cable
Set the extension cable name.
(Entered at user's discretion. Do not
use the one for the CPU module.)
Up to 16 characters
Slots
Set the number of slots of the main
base unit or extension base unit.
This setting must be done for all base
units.
2, 3, 5, 8, 10, or 12