![Mitsubishi Electric QJ71GF11-T2 User Manual Download Page 229](http://html.mh-extra.com/html/mitsubishi-electric/qj71gf11-t2/qj71gf11-t2_user-manual_1811847229.webp)
227
CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
9
9.
6
D
is
abli
ng/
Enab
ling
Reserv
ed S
tat
ion S
et
ting
(2) Selecting the target module in the "Reserved Station Function Enable" window
Reservation of multiple slave stations can be temporarily cancelled through the "Reserved Station Function
Enable" window all at once.
(a) Temporarily canceling a reservation
●
Parameter setting
The network parameter does not reflect the temporary cancellation of reserved station specification.
●
When the master station is reset or the system is powered off
The disabled reserved station setting is ignored, and the slave station returns to the status set by the network parameter
of the master station.
●
When a station for which the reserved station setting has been temporarily disabled is disconnected from the network
The following status differs between the master station and local stations after the CPU module on the master station is
reset or the system is powered off.
• ERR. LED status
• Reserved station setting status (SW00C0 to SW00C7) and Reserved station cancel setting status (SW0180 to
SW0187)
The difference can be corrected by the following procedure.
1. Reconnect the disconnected station.
2. Disable the reserved station setting, and then enable the reserved station setting again.
1.
Connect a slave station specified as a reserved
station to the network.
2.
Connect GX Works2 to the CPU module.
3.
Start the CC-Link IE Field Network diagnostics from
the menu.
[Diagnostics]
[CC IE Field Diagnostics]
4.
Click the
button in the "CC IE
Field Diagnostics" window.
The "Reserved Station Function Enable" window opens.
5.
In "Reserved Station List", click the number of the
target station. The text turns red and the
background turns orange.
:
Only reserved stations can be selected. The
background of a reserved station number is displayed in
light blue.
6.
Clicking the
button will temporarily cancel
the reservation.
7.
Debug the slave station that has been added.
Ex.