4.4 Wiring
4.4.2 External wiring
4
SETUP AND PROCEDURES BEFORE OPERATION
4.4.2
External wiring
(1) For voltage output
*1 For wire, use the shielded twisted pair cable.
*2 If noise or ripple occurs for external wiring, connect a capacitor with the value of 0.1 to 0.47 F (with-
stand voltage 25V or higher) to the input terminal of an external device.
(2) For current output
*1 For wire, use the shielded twisted pair cable.
*2 If noise or ripple occurs for external wiring, connect a capacitor with the value of 0.1 to 0.47 F (with-
stand voltage 25V or higher) to the input terminal of an external device.
The Q66DA-G needs to be powered on 30 minutes prior to operation for compli-
ance to the specification (accuracy).
Similarly, power on 30 minutes prior to offset/gain setting or after online module
replacement.