4.9
Error Time Output Mode Setting
(1) What is the error time output mode setting?
This setting determines whether to clear or hold the outputs to the following Q series
modules when a stop error occurs in the C Controller module.
• Output modules
• I/O combined modules
• Intelligent function modules
• Interrupt modules
(2) Error time output mode setting
The error time output mode is set in "I/O assignment" in << I/O assignment settings>>
of C Controller setting utility.
1) Configure the I/O assignment settings.
2) Select .
3) Select "Clear" or "Hold" for each slot. (The default is "Clear".)
(3) Precautions
The error time output mode setting takes effect when:
• The C Controller system is powered on.
• The C Controller module is reset.
Figure 4.13 Error time output mode setting
Q12DCCPU-V
Q06CCPU-V
Q06CCPU-V-B
Detailed settings
1) Configure I/O assignment settings.
2) Click the Detailed settings button.
3) Select "Clear" or "Hold."