background image

7

GB

D

F

I

NL

E

P

GR

RU

TR

Dimension C

338

Dimension D

143

143+

α

3.1. Securing installation and service space

[Fig. 3.1.1] (P.2)

Select a blowout direction suited for room shape, installation site and so on.

Piping, wiring and maintenance are all done on the bottom and the side. So,

secure the space given above for such work. Also, taking into consideration

serviceability and safety in hanging, secure as large space as possible.

4. Fixing hanging bolts

4.2. Ceiling hole and hanging bolt positions

Use the gage supplied with the panel to fix hanging bolts so that the unit body

and ceiling hole are positioned in place as shown in the figure below. For how

to use the gage, refer to the instruction manual supplied with the panel.

Notes:

• The gage may expand or shrink with changes in the temperature and

humidity. First be sure to check the product dimensions, and then use

the gage.

• The ceiling hole is adjustable as shown in the figure below. Align the

centers of both ceiling hole and unit body so that the unit body is not

biased to the ceiling hole and that the gaps between the ceiling hole

edges and the unit body’s external dimensions come to be identical.

Use M10 hanging bolts (for all bolts). (field supply)

Each hanging bolt must extrude Cmm from the ceiling. It is possible to slide the

unit body 15 mm max. within part of the heights of the unit body and decorative

panel in order to make fine installation adjustments to the finished ceiling sur-

face. Sliding the unit body and incorporating a high-performance filter requires

the dimensions given in the figure below. To this, attach nuts which will fix a

hanging bracket as shown in the figure.

[Fig. 4.2.1] (P.2)

A

Nut

B

Washer (supplied with the unit body)

C

Hanging bolt ø10 (M10 screw)

D

Ceiling hole dimensions

E

Hanging bolt pitch

F

Hanging bolt

G

Finished ceiling surface

H

Hanging bracket

A

Split flow duct end connection

B

Split flow duct end connection (ø200 knockout on both sides)

C

Fresh air intake (ø150 knockout)

D

Fresh air intake

E

To be cut

F

4-ø2.9 mounting hole

G

4-ø2.9 mounting hole

Notes:

• Affixed on the back surface of each split flow duct end connection is

insulating material. Use a cutter knife to cut the insulating material along

the end connection.

• To adjust the fresh air intake capacity, cut the two places as shown in the

figure at right, and rotate the intake.

3.3. Combining  indoor  units  with  outdoor

units

For combining indoor units with outdoor units, refer to the outdoor unit installation

manual.

3.2. Split flow duct end connection - fresh

air intake

[Fig. 3.2.1] (P.2)

Knockouts are provided at each position as shown in the figure. Use them for

your purposes when installing the unit.

338+

α

(353 Max.)

α

 indicates a range of 0 to 15 mm.

4.1. Fixing hanging bolts

(Use M10 hanging bolts. The bolts should be procured locally.)

(Give site of suspension strong structure.)

Hanging structure

Ceiling: The ceiling structure varies from building to one another. For detailed

information, consult your construction company.

1

Reinforcing the ceiling with additional members (edge beam, etc.) must be

required to keep the ceiling at level and to prevent the ceiling from vibrations.

2

Cut and remove the ceiling members.

3

Reinforce the ceiling members, and add other members for fixing the ceiling

boards.

For wooden construction

Use the tie beam (for one story building) or second-floor beam (for two story

building) as strength members.

To  hang  the  air-conditioner,  use  a  hard  square  timber  of  more  than

6 cm if the distance between beams is less than 90 cm and a hard square

timber of more than 9 cm if the distance between beams is less than 180 cm.

[Fig. 4.1.1] (P.2)

A

Ceiling board

B

Edge beam

C

Tie beam

D

Square timber for hanging the air conditioner

E

Pitch

For reinforced concrete construction

As shown in the figure below, fix the hanging bolts, or use square timbers to fix

the hanging bolts.

[Fig. 4.1.2] (P.2)

F

Insert: 100 to 150 kg (1 piece) (field supply)

G

M10 hanging bolt (field supply)

H

Reinforcement

Product Weight (kg)

Model name 20 · 25 · 32

40 · 50

63 · 80

100 · 125

A

1060

1300

1650

2000

B

More than 1000

C

More than 500

D

Lap: 20

E

360

Model name

20 · 25

32

40

50

63

80

100 · 125

Body frame

24

25

33.5

35

39

41

56

Panel

7

7

8

8

10

10

11.5

Model name 20 · 25 · 32

40 · 50

63 · 80

100 · 125

A

1020

1260

1610

1960

B

816

1056

1406

1756

Installation

example

For not sliding unit body

For sliding unit body

Summary of Contents for PLFY-P-VLMD-A

Page 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Page 2: ...2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 H D 630 E 550 40 40 D A E B 102 102 A A B B C F B A D 50 10 G C A Nut B Washer supplied with the unit body C Hanging bolt ø10 M10 screw D Ceiling hole dimensions E Hanging bolt pitch F Hanging bolt G Finished ceiling surface H Hanging bracket A D C B A Drain pipe side B Unit body C Packing cap D Lifting machine B A B Indoor unit s bottom surfa...

Page 3: ...INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation D I C H G K I J 3 C 30 cm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E...

Page 4: ...ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Address board Fig 8 2 5 G I J J J K K K F J J L K H 1 3 L1 L2 L4 l L3 2 G Outdoor unit H Earth I BC controller J Indoor unit K Remote controller L Non polarized 2 wire Fig 8 2 1 A A C TB5 TB5 S M1M2 S M1M2 C B TB3 M1M2 A A C TB5 TB15 TB5 TB15 S M1M2 S M1M2 B TB3 M1M2 2 1 C 2 1 Fig 8 ...

Page 5: ...y limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is install...

Page 6: ...eteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R407C the refrigerant may deteriorated If water is mixed in the R407C the refrigerator oil may deteriora...

Page 7: ...the back surface of each split flow duct end connection is insulating material Use a cutter knife to cut the insulating material along the end connection To adjust the fresh air intake capacity cut the two places as shown in the figure at right and rotate the intake 3 3 Combining indoor units with outdoor units For combining indoor units with outdoor units refer to the outdoor unit installation ma...

Page 8: ... Packing cap D Lifting machine Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity it is necessary to use pipe size and insulating material s thickness more than those given in the table above 3 If there are customer s specificati...

Page 9: ...e the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil et...

Page 10: ...cc D Water E Filling port Building clinic hospital or communications station without noise supposedly generated from inverter equipment private power gen erator high frequency medical equipment radio used communications equipment and so on Residence or independent store without noise Facility example for noise judgment All facilities VCTF VCTFK CVV CVS VVR VVF VCT or shielding wire CVVS or CPEVS S...

Page 11: ...ol board to ON The setting of SW1 7 and SW1 8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF 8 2 Connecting remote controller indoor and outdoor transmission cables Remote contoroller is optionally available Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For specific...

Page 12: ...t the contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: