9901025-2
Page 13 of 21
connection if removed earlier. Ensure cables are not trapped inside and refit retaining
screw. The Filter Indicator Schedule can now be changed from its default setting if
required (see page 15). Replace the bottom access panel, air inlet grilles (with filters)
and plastic end caps (see “To gain access inside the Air Curtain” page 7). Power-up
both the Outdoor Unit and Air Curtain and re-check the operation of the unit
Manual Room Control
On the Mitsubishi Electric Interface PCB the BMS Fan-Run Connection should be
'parked' at position CNX5 (green), see Wiring Diagram – Page 10. The dip switch
settings should be as follows:
1
2
3
4
5
6
ON
OFF
SW1
7
8
Black rectangle indicates moveable head of dip switch
1
2
3
4
5
6
ON
OFF
SW2
7
8
1
2
3
4
5
6
ON
OFF
SW3
7
8
On the Thermoscreens Manual Room Control set the Fan On/Off switch to Off '0' and
the Ambient/Heat switch to Ambient ' ' Fan only. Switch on the electrical power to
the Mitsubishi Electric outdoor unit and the Air Curtain. WARNING! Interface PCB will
have 230 volts on it.
Communication between the Mitsubishi Electric Outdoor Unit and the Air Curtain
commences approximately 30 seconds after power-up. After this time use the Room
Control to switch on the fans. Once the air curtain fans are operating check that they
run at Low (I), Medium (II) and High (III) speeds using the manual 3 speed fan switch
inside the left hand end of the air curtain. Check there is no mechanical noise coming
from the fans and that all fans are working. Select the fan speed appropriate to the
site conditions and leave on this setting.
Using the Manual Room Control set the Ambient/Heat switch to Heat ' ' and the heat
setting switch to Full Heat '
'. Check that the air stream from the discharge warms
up across the whole length of the air curtain after approximately 20 minutes and that
the air stream reaches right down across the doorway with the door open or closed.
Use the Manual Room Control to test the different heat settings. LEDs 1-5 on the
Interface PCB should be lit as follows.
•
LED 1 indicates that there is power to the air curtain
•
LEDS 2-5 indicate the different heating settings
selected via the Manual Room Control heat setting
switch
Fan On/Off switch
Heat setting switch
•
automatic
•
full
heat
•
half
heat
Ambient/Heat switch
Room Control
I 0
Heat setting
LEDs lit
ambient 1
half heat
1,3
full heat
1,3,5
automatic 1,2,3,5