19
GB
[Fig. 7.3.4] (P.9)
A
To 3-phase power supply
B
to terminal block for indoor-outdoor transmission line connection
[Fig. 7.3.5] (P.9)
A
B
<Temperature sensor extended with a shielded cable>
C
A
Indoor unit control board (No.1)
B
Indoor unit control board (No.2)
C
CN20 (Red)
D
Temperature sensor cable
E
Cable that is supplied with the temperature sensor
F
Supply air temperature sensor cable
<A> Connect the cable to CN20.
<B> Secure the cable with the clamps.
<C> Use closed end connectors to connect the two cables.
<D> Connect the shield to the ground terminal screw.
(the screw is attached in the control box.)
<E> Temperature sensor extended with a shielded cable
<F> Supply air temperature sensor cable is bundled inside the control box.
7.4. Setting addresses
(Be sure to operate with the main power turned OFF.)
1. An address must be set for this system. Furthermore, the address setting range differs depending on the unit.
2. When group operation will be performed, set the addresses according to the table below.
* Group operation means to operate multiple indoor units using one remote controller (or 2 remote controllers).
Note 1: If an address is a duplicate of an indoor unit or outdoor unit of another refrigerant circuit system, set it to another address, which is within the setting range and is
not in use.
Note 2: To set the address of an outdoor unit to “100,” set it as 50.
Note 3: The outdoor units OC and OS of the same refrigerant circuit system are differentiated automatically.
The order of OC and OS becomes from the one with the highest capacity. (If the capacity is the same, the order is from the one with the lowest address.)
Note 4: P750·P900-F model indoor units are equipped with two indoor controllers (control boards). Assign an address so that the No. 2 control board address equals the
No. 1 control board address plus 1. (Factory setting: No.1=01, No.2=02)
3. The address (SW 12 and 11) setting becomes a combination of the 10’s digit (SW 12) and 1’s digit (SW 11) as shown in the examples below.
Example: With the address “03,” the tens digit (SW 12) is “0,” and the ones digit (SW 11) is “3.”
With the address “25,” the tens digit (SW 12) is “2,” and the ones digit (SW 11) is “5.”
4. After setting an address, make sure you enter the address in the Address No. field on the product name plate with, for example, a permanent marker.
7.5. When using other than the internal sensor of the unit to detect the room temperature
•
When the internal sensor of the remote controller will be used, set each of SW 1-1 and SW 3-8 to ON.
•
Some types of remote controller do not have an internal remote sensor. In such a case, set the internal sensor of the unit to detect the room temperature.
•
When using the internal sensor of the remote controller, attach the remote controller to a place where it is possible to detect room temperature.
•
When using the supply air temperature to control the room temperature, the built-in sensor on the remote controller cannot be used.
Wiring using the supplied temperature sensor
Wiring using the supply air temperature sensor
Unit or controller
Mark
Address
setting
range
Setting procedure
Address set
at time of
shipment
Model
Indoor unit
Main/Sub
IC
01 to 50
Note 1
Note 4
For the indoor units of the same group, set the lowest address for the indoor unit to be
used as the main, and set consecutive numbers for the addresses of indoor units.
00
Note 4
LOSSNAY/Outdoor air processing
unit
LC
01 to 50
Note 1
Set any address after setting all of the indoor units.
00
MA remote controller
MA
An address does not need to be set. (However, when operation is to be performed with two remote
controllers, the main/sub selector settings need to be set.)
Main
Outdoor unit
OC
OS
51 to 100
Note 2
Set an address equivalent to the lowest indoor unit address in the same refrigerant
circuit 50. Set consecutive numbers for the addresses of outdoor units in the
same refrigerant circuit system. OC and OS are differentiated automatically. (Note 3)
00
System
controller
Centralized
controller
TR, SC
0, 201 to
250
Any address within the address range on the left.
000
System remote
controller
SR, SC
201 to 250
Any address within the address range on the left.
201
Schedule timer
(M-NET
compatible)
ST, SC
201 to 250
Any address within the address range on the left.
202
ON/OFF remote
controller
AN, SC
201 to 250
Set an address that is the smallest group number you want to c “200”.
201
Group remote
controller
GR, SC
201 to 250
Set an address that is the smallest group number you want to c “200”.
LM adapter
SC
201 to 250
Any address within the address range on the left.
247
00gb_WT05474X02_7.book Page 19 Wednesday, July 22, 2009 5:29 PM
Summary of Contents for PFAV-P250-500-750VM-E
Page 119: ......