TECHNICAL & SERVICE MANUAL

SPLIT-TYPE, AIR CONDITIONERS

CONTENTS

1. COMBINATION OF AND OUTDOOR UNIT···3

2. TECHNICAL CHANGE···························3

3. PART NAMES AND FUNCTIONS··········3

4. SPECIFICATIONS ··································5

5. DATA·······················································9

6. OUTLINES AND DIMENSIONS ···········20

7. WIRING DIAGRAM·······························24

8. REFRIGERANT SYSTEM DIAGRAM ········25

9. OPERATION FLOW-CHART················27

10. MICROPROCESSOR CONTROL ········30

11. TROUBLE SHOOTING ·························36

12. DISASSEMBLY PROCEDURE·············39

13. PARTS LIST··········································41

14. OPTIONAL PARTS·······························45

<Indoor unit>

[Model names]

[Service Ref.]

PE-3EJA

PE-3EJA

2

.TH

PE-3EJA

3

.TH

PE-4EJSA

PE-4EJSA

2

.TH

PE-5EJSA

PE-5EJSA

2

.TH

PE-6EJSA

PE-6EJSA

2

.TH

No. OC155

REVISED  EDITION-B

Indoor unit

Ceiling Concealed

Series PE

MITSUBISHI ELECTRIC

12

11

10

9

8

7

6

5

4

3

2

1

29

28

27

26

25

24

23

22

21

20

19

18

TIMER

TEMP

TIMER/TEMP.

UP

DOWN

POWER

COOL

ON/OFF

MODE

SELECT

FAN

SPEED

TIMER
MODE

DRY

FAN

HIGH

LOW

AUTO
STOP

START

Remote controller

PE-3EJA

3

.TH added in REVISED

EDITION-B.
Please destroy OC155 REVISED
EDITION-A.
This manual does not cover the
following outdoor units.
When servicing them, please refer
to the following service manual and
this manual in a set.
[Service Ref.]
OC152 REVISED EDITION-A

PU-3VJA

1

.TH, 3YJA

1

.TH

PU-4VLJSA

1

.TH, 4YJSA

1

.TH

PU-5YJSA.TH
PU-6YJSA.TH

OC127 REVISED EDITION-A

PU-3NJA

1

PU-4TJSA

2

OC199

PU-5TJSA

1

PU-6TJSA

1

OC206

PU-3VJC.TH, 3YJC.TH

OC155-B--1.qxp  7/26/00 4:42 PM  Page 1

Summary of Contents for PE-3EJA

Page 1: ...SA PE 6EJSA2 TH No OC155 REVISED EDITION B Indoor unit Ceiling Concealed Series PE MITSUBISHI ELECTRIC 12 11 10 9 8 7 6 5 4 3 2 1 29 28 27 26 25 24 23 22 21 20 19 18 TIMER TEMP TIMER TEMP UP DOWN POWER COOL ON OFF MODE SELECT FAN SPEED TIMER MODE DRY FAN HIGH LOW AUTO STOP START Remote controller PE 3EJA3 TH added in REVISED EDITION B Please destroy OC155 REVISED EDITION A This manual does not cov...

Page 2: ......

Page 3: ...CITY 24 600 Btu h 7 200 W PU 3VJA1 TH PU 3YJA1 TH 2 2kW PU 3YJA1 TH 2 4kW PU 3YJC TH 25 600 Btu h 7 500 W PU 3VJC TH PU 3YJC TH OUTDOOR UNIT COMPRESSOR OUTPUT Change points Service Ref PE 3EJA2 TH PE 3EJA3 TH PE 4EJSA2 TH PE 5EJSA2 TH PE 6EJSA2 TH VJA1 TH YJA1 TH NJA1 VLJSA1 TH YJSA1 TH TJSA2 YJSA TH TJSA1 YJSA TH TJSA1 VJC TH YJC TH 3 4 5 Outdoor unit 6 2 TECHNICAL CHANGE Differences with PE 3EJA...

Page 4: ... change between cooling ventilation and DRY opera tion modes One of three green lamps lights to indi cate mode in effect ON OFF button Pushing button starts oper ation Pushing again stops operation Green lamp remains lit during operation UP and DOWN buttons Temperature control While TEMP green lamps is lit Use UP and DOWN buttons to set desired temperature between 18 and 29 C Timed operation While...

Page 5: ... 777 22 26 777 918 49 5 69 7 46 48 48 50 R1 785 31 690 27 1 6 428 16 7 8 46 101 W7 PU 3JA type 2 2 32 38 0 085 50 1 765 50 1 765 52 53 870 34 1 4 850 33 7 16 73 161 PE 4EJSA 2 TH 9 800 33 400 10 900 37 200 9 400 32 000 3 59 4 69 PE 4EJSA 2 TH 0 3 27 34 953 1 200 27 34 953 1 200 62 6 35 62 6 35 54 58 54 58 R1 1 055 41 1 2 690 27 1 6 428 16 7 8 58 128 W7 PU 4JSA type 2 7 32 38 0 065 0 065 95 3 352 9...

Page 6: ...0 1 482 62 6 35 62 6 35 54 58 54 58 R1 1 255 49 7 16 690 27 1 6 428 16 7 8 72 159 PU 5YJSA TH 5TJSA1 3 5 W6 0 10 0 10 100 3 530 100 3 530 55 55 970 38 3 16 1 258 49 1 2 114 282 PE 6EJSA2 TH 14 000 47 800 15 200 51 900 13 400 45 700 5 65 6 58 PE 6EJSA2 TH 0 4 34 42 1 200 1 482 34 42 1 200 1 482 62 6 35 62 6 35 54 58 54 58 R1 1 255 49 7 16 690 27 1 6 428 16 7 8 72 159 PU 6YJSA TH 6TJSA1 4 2 4 0 W6 0...

Page 7: ...00 6 700 23 000 3 41 3 76 PE 3EJA 3 TH Galvanized sheets 0 2 19 22 671 777 22 26 777 918 49 5 69 7 Remote controller built in 46 48 48 50 R1 785 31 690 27 1 6 428 16 7 8 46 101 PU 3VJC TH 3YJC TH 3NJA1 Munsell 5Y 7 1 Capillary tube V 2 2 Y 2 4 N 2 2 W6 32 38 0 085 50 1 765 50 1 765 52 53 870 34 1 4 295 24 11 5 8 add 1 850 33 7 16 73 161 50Hz 60Hz 60Hz 50Hz 60Hz 50Hz 60Hz W D H 50 60Hz 50Hz 60Hz 50...

Page 8: ...PU 5TJSA1 PE 6EJSA 2 TH PU 6YJSA TH PU 6TJSA1 50Hz 60Hz Power supply 1 phase Current Input Starting current Outdoor unit PE 3EJA2 TH PE 3EJA3 TH 1 07 0 23 2 4 PU 3 V 220V 50Hz V 230V 50Hz V 240V 50Hz N 220V 60Hz 1 41 0 30 2 6 PU 4 PE 4EJSA2 TH 1 07 0 24 2 5 PU 3 PE 3EJA2 TH PE 3EJA3 TH 1 40 0 31 2 6 PU 4 PE 4EJSA2 TH 1 07 0 25 2 6 PU 3 PE 3EJA2 TH PE 3EJA3 TH 1 39 0 32 2 6 PU 4 PE 4EJSA2 TH 1 47 0...

Page 9: ... 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F T C 0 81 0 82 0 83 0 83 0 84 0 86 0 84 0 85 0 86 0 86 0 87 0 89 0 90 0 92 0 93 0 93 0 94 0 96 0 93 0 95 0 96 0 97 0 97 0 99 0 96 0 99 1 00 1 00 1 01 1 04 1 03 1 06 1 07 1 08 1 08 1 11 1 04 1 06 1 08 1 08 1 09 1 12 1 10 1 12 1 14 1 15 1 16 1 20 1 11 1 14 1 15 1 16 1 17 1 21 1 16 1 19 1 21 1 2...

Page 10: ... 22 C 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F ...

Page 11: ...4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F T C 0 81 0 82 0 83 0 83 0 84 0 86 0 84 0 85 0 86 0 86 0 87 0 89 0 90 0 92 0 93 0 93 0 94 0 96 0 93 0 95 0 96 0 97 0 97 0 99 0 96 0 99 1 00 1 00 1 01 1 04 1 03 1 06 1 07 1 08 1 08 1 11 1 04 1 06 1 08 1 08 1 09 1 12 1 10 1 12 1 14 1 15 1 16 1 20 1 11 1 14 1 15 1 16 1 17 1 21 1 16 1 19 1 21 1 22 1 ...

Page 12: ... F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F T C 0 81 0 82 0 83 0 83 0 84 0 86 0 84 0 85 0 86 0 86 0 87 0 89 0 90 0 92 0 93 0 93 0 94 0 96 0 93 0 95 0 96 0 97 0 97 0 99 0 96 0 99 1 00 1 00 1 01 1 04 1 03 1 06 1 07 1 08 1 08 1 11 1 04 1 06 1 08 1 08 1 09 1 12 1 10 1 12 1 14 1 15 1 16 1 20 1 11 1 14 1 15 1 16 1 17 1 21 1 16 1 19 1 21 1 22 1 2...

Page 13: ... 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F 60 8 F 64 4 F 66 2 F 67 F 68 F 71 6 F T C 0 81 0 82 0 83 0 83 0 84 0 86 0 84 0 85 0 86 0 86 0 87 0 89 0 90 0 92 0 93 0 93 0 94 0 96 0 93 0 95 0 96 0 97 0 97 0 99 0 96 0 99 1 00 1 00 1 01 1 04 1 03 1 06 1 07 1 08 1 08 1 11 1 04 1 06 1 08 1 08 1 09 1 12 1 10 1 12 1 14 1 15 1 16 1 20 1 11 1 14 1 15 1 16 1 17 1 21 1 16 1 ...

Page 14: ... 45m 148ft 0 884 0 850 50m 164ft 0 875 0 840 Refrigerant piping length one way PE 3EJA2 TH PE 3EJA3 TH Service Ref PE 4EJSA2 TH PE 5EJSA2 TH PE 6EJSA2 TH 5m 16ft 1 0 1 0 1 0 1 0 10m 33ft 0 971 0 980 0 971 0 960 15m 49ft 0 950 0 966 0 950 0 933 20m 66ft 0 931 0 952 0 931 0 908 25m 82ft 0 913 0 939 0 913 0 885 30m 98ft 0 896 0 926 0 896 0 894 35m 115ft 0 914 0 880 0 845 40m 131ft 0 902 0 864 0 828 4...

Page 15: ...100 3 76 1 60 220 1 41 PU 3NJA1 1 60 220 17 6 2 20 0 44 73 2 54 2 1 3 5 27 19 14 2 35 24 Cooling 9 800 3 59 1 50 220 1 41 PU 4YJSA1 TH 3 50 380 5 7 1 91 0 54 77 4 50 3 9 2 5 27 19 14 6 35 24 Cooling 10 900 4 69 1 60 220 1 95 PU 4TJSA2 3 60 220 12 2 2 14 0 51 77 5 54 9 6 7 5 27 19 15 3 35 24 PE 3EJA 2 TH PE 4EJSA 2 TH PE 3EJA 2 TH PE 4EJSA 2 TH Total Electrical Circuit Refrigerant Circuit Indoor si...

Page 16: ...20 2 50 PU 6YJSA TH 3 50 380 8 63 1 95 0 44 77 8 50 8 1 7 5 27 19 14 5 35 24 Cooling 12 100 5 10 1 50 220 2 50 PU 5YJSA TH 3 50 380 8 15 1 86 0 48 72 2 49 3 0 9 5 27 19 15 5 35 24 Cooling 15 200 6 58 1 60 220 1 99 PU 6TJSA1 3 60 220 18 70 2 01 0 40 81 52 1 0 5 5 27 19 14 1 35 24 PE 5EJSA2 TH PE 6EJSA2 TH PE 5EJSA 2 TH PE 6EJSA 2 TH Total Electrical Circuit Refrigerant Circuit Indoor side Outdoor s...

Page 17: ... 52 4 4 5 5 27 19 15 0 35 24 W kW V A V A MPa MPa m kgf F kgf F 20 8 4 7 22 4 4 5 Cooling 8 100 3 76 1 60 220 1 41 PU 3NJA1 1 60 220 17 6 2 20 0 44 73 2 54 2 1 3 5 27 19 14 2 35 24 PE 3EJA 3 TH PE 3EJA 3 TH Total Electrical Circuit Refrigerant Circuit Indoor side Outdoor side D B W B D B D B W B Intake air temperature Intake air temperature The unit of pressure has been changed to Mpa based on SI ...

Page 18: ...e 150 100 50 Hi Lo 0 1 0 0 95 1 05 0 9 2022 25 30 3537 20 22 25 30 35 37 40 External static pressure Pa 1Pa 0 1mmAq Correction factor Airflow m min 60Hz Capacity Input 50Hz 50Hz Recommended range 150 100 50 Hi Lo 0 1 0 0 95 0 9 16 18 20 22 16 18 20 22 External static pressure Pa 1Pa 0 1mmAq Airflow m min 1m min 35 3CFM Correction factor Airflow m min 60Hz 60Hz Recommended range 150 100 50 Hi Lo 0 ...

Page 19: ...1 05 0 9 27 30 35 40 45 Correction factor Airflow m min 60Hz Capacity Input Airflow m min 50Hz 50Hz Recommended range 150 100 50 Hi Lo 0 1 0 0 95 1 05 0 9 27 30 35 40 45 48 27 30 35 40 45 48 50 External static pressure Pa 1Pa 0 1mmAq Airflow m min Recommended range 150 100 50 Hi Lo 0 27 30 35 40 45 50 External static pressure Pa 1Pa 0 1mmAq Correction factor Airflow m min 60Hz 1 0 0 95 1 05 0 9 27...

Page 20: ...let duct connection 12 3 1 8 holes 15 Air outlet 16 Mounting plate 17 Air outlet duct flange 18 Heat insulator t10 3 8 19 Service space opening in the ceiling 20 Service panel Room temperature thermistor 21 Duct earth Unit mm inch 11 11 105 35 70 44 50 59 75 35 3 2 2 3 8 60 265 10 1 2 40 155 155 155 20 13 16 10 3 8 600 24 100 70 300 900 36 145 24 5 145 22 5 20 672 26 1 2 4 3 16 13 16 510 20 1 8 33...

Page 21: ... 16 530 7 7 8 2 3 4 600 24 11 1 Refrigerant pipe flared connection 9 52 3 8 2 Refrigerant pipe flared connection 19 05 3 4 3 Electrical parts box 4 Drain pan 5 Drain pipe connection R1 male 6 Service panel Indoor coil thermistor 7 Room temperature thermistor 8 Heat insulator t10 3 8 9 Air intake duct flange 10 Air intake 11 Wiring entry 2 22 7 8 holes 12 Suspension bolt holes 4 12 1 2 13 34 3 1 8 ...

Page 22: ... 300 900 36 11 13 16 530 7 7 8 600 24 1 Refrigerant pipe flared connection 9 52 3 8 2 Refrigerant pipe flared connection 19 05 3 4 3 Electrical parts box 4 Drain pan 5 Drain pipe connection R1 male 6 Service panel Indoor coil thermistor 7 Room temperature thermistor 8 Heat insulator t10 3 8 9 Air intake duct flange 10 Air intake 11 Wiring entry 2 22 7 8 holes 12 Suspension bolt holes 4 12 1 2 13 4...

Page 23: ...9 8 7 6 5 4 3 2 1 29 28 27 26 25 24 23 22 21 20 19 18 TIMER TEMP TIMER TEMP UP DOWN POWER COOL ON OFF MODE SELECT FAN SPEED TIMER MODE DRY FAN HIGH LOW AUTO STOP START Exposed remote controller cable Cable can be connected only to the top of the remote controller Right side left side and buttom are not possible Remote controller cable Conduit tube local arrangement Switch box local arrangement Set...

Page 24: ...gram above are Terminal block Connector 4 Emergency operation If remote controller or microcomputer fails but there is no other trouble emergency operation is possible by setting dip switch SW3 I B on the indoor con troller board Check items 1 Compressor and fan 2 Check the trouble position using self diagnostic function If the result of self diagnosis indicates protective device such as freeze pr...

Page 25: ...sure switch Check plug Ball Valve With service port Capillary tube For injection Capillary tube O D 3 2 I D 1 8 L800 2pcs Indoor heat exchanger Refrigerant pipe 9 52 3 8 with heat insulator option Ball valve with service port Flow of refrigerant Flow of refrigerant D P R Discharge pressure regulator Capillary tube Compressor Accumulator O D 3 2 oI D 1 8 o L800 o2pcs Ball valve Low pressure switch ...

Page 26: ...nnection Flared connection Flexible tube Compressor Only PU 4TJSA 4YJSA Accumulator Ball Valve Charge plug Low pressure switch High pressure switch Check plug Ball Valve With service port Capillary tube For injection Capillary tube O D 3 2 I D 1 8 L1360 2pcs Capillary tube PU 5Y TJSA O D 4 0 oI D 2 4 L400 PU 6Y TJSA O D 4 0 oI D 2 4 L200 Ball valve with service port Capillary tube PU 5Y TJSA O D 4...

Page 27: ...et time Elapsed time 0 Set time Elapsed time 0 Note 1 Refer to page 33 for timer mode details Note 2 The unit starts operation by pressing the ON OFF switch when unit is OFF During operation the unit stops operation by pressing the ON OFF switch In addition operation can be turned ON OFF with the centralized remote controller or the remote switch Note 3 The factors which cause abnormal operation m...

Page 28: ...S YES YES YES YES YES YES YES YES YES YES YES NO NO NO NO Note 6 Note 7 Note 8 Compressor thermostat ON Allowance release Allowanse Allowanse set 6 minute time delay Coil frost protection check mode Continue 1 minute Fan speed LOW Fan speed LOW 5 minutes elapse Outdoor unit abnor mality check mode Note 6 The thermostat is continuously ON during the test run Note 7 Refer to page 31 for coil frost p...

Page 29: ... or below NO NO NO NO NO NO NO YES YES YES YES YES YES YES YES YES Note 6 Note 10 Note 6 Note 11 Note 12 Note 12 3 minute time delay Note 10 When the room temperature is 18 C or below the compressor can not turn ON When the room temperature rises to 19 C or above the compressor will start operation after a 3 minute time delay Note 11 Refer to page 32 for the compressor operation time Note 12 In DR...

Page 30: ... fan motor ON OFF Fan ON OFF Fan speed HIGH LOW Emergency stop OUTPUT to indoor unit INPUT from indoor unit INPUT to remote controller Transmits and receives orders REMOTE CONTROLLER OUTPUT to remote controller INDOOR CONTROLLER BOARD Receives orders from remote controller and temperature data from indoor unit Processes orders and data Transmits the power of indication lamp to remote controller Co...

Page 31: ...he start condition is satisfied again during the first 10 minutes of compressor operation both the indoor and outdoor units stop and the remote controller displays this occurrence Termination conditions Coil frost protection is released when the start condition is not satisfied again during the allowance or when the COOL mode stops or changes to another mode How to operate 1 Press POWER ON OFF but...

Page 32: ...t An abnormality in the outdoor unit can not be detected in DRY operation How to operate 1 Press POWER ON OFF button 2 Press MODE SELECT button to set operation mode to DRY 3 Check lamp is ON and set desired temperature with UP or DOWN but ton NOTES 1 When lamp is ON press DISPLAY SELECT button to change the display to temperature mode 2 Set temperature changes by 1 C in the range 18 29 C each tim...

Page 33: ...e lapse of time the timer lamps turn OFF one by one showing the remain ing time 4 To cancel the AUTO START timer and keep the unit OFF press the TIMER MODE button To cancel the AUTO START timer and start operation press the POWER ON OFF button TIMER POWER TIMER POWER MITSUBISHI ELECTRIC 12 11 10 9 8 7 6 5 4 3 2 1 29 28 27 26 25 24 23 22 21 20 19 18 TIMER TEMP TIMER TEMP UP DOWN POWER COOL ON OFF M...

Page 34: ...available by setting the dip switch on the indoor controller board Check items Make sure the compressor and the fans are running normally Locate the trouble with the self diagnostic function If the self diagnostic function indicates that the protec tion device such as coil frost protection is functioning the sources must be removed before attempting emer gency operation Emergency operation ON OFF ...

Page 35: ...ng JR04 changes the speed from Extra Low to Low 5 JR5 Jumper wire for detecting abnormalities in the outdoor unit Cutting JR05 makes this detection unavailable Occurrence of abnormality can not be detected 6 JR6 Jumper wire for auto restart function Cutting JR06 makes the auto restart function available 2 Dip switch 1 SW1 Function switch SW1 1 Switch for power supply ON 220V OFF 230V 240V SW1 2 Sw...

Page 36: ...etting Check wiring Outdoor unit Wrong wiring between indoor outdoor units Outdoor unit abnormality detection Malfunction of outdoor coil thermistor Reversed phase detected Check wiring Check outdoor unit Check outdoor coil thermistor Unit No 1 Unit No 2 Room temperature thermistor RT1 Poor connector contact Thermistor malfunction Check connector Check thermistor No trouble replace indoor controll...

Page 37: ...re is connected incorrectly Indoor outdoor connect ing wire shorts Compressor protector is damaged Dicer is broken Remote controller is damaged Transmission wire is poorly connected Transmission wire is damaged Connector is poorly connected 2 OTHER TROUBLES AND CAUSES ...

Page 38: ... Motor terminal or Relay connector Normal PE EJ S A 3EJA2 3EJA3 Abnormal WHT BLK 46 38 Open or short 17 25 1 2 3 1 2 3 4 CNT T CN4T RED BRN WHT YLW BLK BLU YLW RED ORN Capacito WHT BLK BLU Protector 1 2 3 4 5 6 7 1 3 5 Parts name Check points 5EJSA2 6EJSA2 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperature Resistance K Thermistor Characteristic graph Room temperat...

Page 39: ...w See Photo 2 Indoor controller board Transformer Run capacitor Fuse 6 3A Terminal block Room temperature thermistor See Photo 3 Photo 2 Photo 3 3 Removing the indoor coil thermistor Remove the drain pan See Photo 1 Remove the electrical parts cover See Photo 2 Remove the set wire of the indoor coil thermistor See Photo 4 Photo 4 Room temperature thermistor Drain pan Set screw for drain pan Electr...

Page 40: ... fan plate See Photo 5 or 6 Unscrew four set screws of the bell mouth and remove the bell mouth See Photo 7 Loosen the set screw of the fan to pull out the sirocco fan See Photo 7 Unscrew the four set screws of the motor fitting and remove the fan motor See Photo 8 Photo 5 Photo 6 Photo 8 Photo 7 Set screw Fan plate Fan casing Fan motor Fan plate Fixture set screw Set screw Fan motor Fittings Bell...

Page 41: ... EJA1 TH EJA2 TH EJA3 TH No Part No Part Name Specification Remarks Drawing No Wiring Diagram symbol Recom mended Q ty E07 027 300 E07 018 500 E07 018 808 E07 018 505 E07 018 700 E07 027 620 PA6V205 E8 INDOOR FAN MOTOR CASING BELL MOUTH SIROCCO FAN LEG FAN PLATE CABINET ASSY AIR OUTLET DUCT FLANGE AIR INTAKE DUCT FLANGE FAN MOTOR LEG MOTOR BEAM RUBBER MOUNT DRAIN PAN HEAT EXCHANGER 1 1 1 1 2 1 1 1...

Page 42: ...96G09 BB02G810G05 MF1 Price Amount Unit Q ty set PE 4 EJSA1 TH EJSA2 TH No Part No Part Name Specification Remarks Drawing No Wiring Diagram symbol Recom mended Q ty E07 028 300 E07 018 505 E07 022 500 E07 018 808 E07 022 700 E07 028 620 PA6V305 EA INDOOR FAN MOTOR RUBBER MOUNT SIROCCO FAN FAN MOTOR LEG MOTOR BEAM BELL MOUTH CASING CABINET ASSY LEG FAN PLATE AIR OUTLET DUCT FLANGE AIR INTAKE DUCT ...

Page 43: ...G12 MF1 Price Amount Unit Q ty set PE 5 EJSA1 TH EJSA2 TH PE 6 EJSA1 TH EJSA2 TH No Part No Part Name Specification Remarks Drawing No Wiring Diagram symbol Recom mended Q ty E07 029 300 E07 018 505 E07 018 500 E07 023 500 E07 018 809 E07 018 808 E07 023 700 E07 029 620 E07 030 620 PA6V400 ED INDOOR FAN MOTOR FAN MOTOR LEG MOTOR BEAM RUBBER MOUNT BELL MOUTH SIROCCO FAN SIROCCO FAN CASING CASING FA...

Page 44: ...S A2 TH EJA3 TH No Part No Part Name Specification Remarks Drawing No Wiring Diagram symbol Recom mended Q ty E07 027 447 E07 006 382 E07 018 351 E07 027 339 E07 006 375 E07 007 375 E07 027 308 E07 027 307 E07 027 426 E07 027 088 E07 027 089 E07 027 087 250V 6 3A 8 0 440VAC 3P L N 2P 1 2 10m 0 5m INDOOR CONTROLLER BOARD FUSE INDOOR FAN CAPACITOR TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK ROOM TEMPE...

Page 45: ... setback operation 2 Setback operation PAC SK65PT Set back operation is useful for reducing running costs e g At a hotel with a 24 hour system 8 00 23 00 Cooling operation with set temperature at 26 C 23 00 8 00 Setback operation with 2 degrees of setback As shown in the chart on the right the set temperature rises 2 degrees automatically during the setback operation When the set back operation en...

Page 46: ... Used to adjust the current time Press AHEAD button to advance the time Each time the button is pressed the time advances by 1 minute and press ing continuously advances 1 minute at a 0 5 second interval When the lower digit of the minutes becomes 0 the indication advances in 10 minute units BACK button is used for reversing the time Each time the button is pressed the time reverses by 1 minute an...

Page 47: ...is given to the last instruction received CENTRAL ON OFF switching by the accessory remote controller is invalidated Operation is controlled by the centralized remote con troller only Initial setting is DUAL LCD Matrix Display This display indicates the operational sta tus of all connected units either by steady lighting or by flashing POWER ON OFF switch Operation ON OFF switch BACK AHEAD buttons...

Page 48: ... 5 6 7 8 9 10 10 9 8 7 6 5 4 3 2 1 Dip switch SW17 Centralized remote controller Power supply board 4 3 Connection method 1 Connections in the power supply cord 1 Connect the power supply cord to the power supply terminal block and fix it in place with a tie lap Connect a single phase 200V AC 220 230 240V to L N As E is the GND terminal be sure to ground the earth wire 2 Connect the transmission l...

Page 49: ...WER SUPPLY CORD POWER SUPLLY 1 Connections in the adapter Box 1 Connect the power supply cord to the terminal block and fix it in place with a tie lap Connect a single phase 200V AC 220 230 240V to L N As is the GND terminal be sure to ground the earth wire 2 Connect the transmission line to the transmission terminal block and fix it in place with a tie lap when a centralized remote controller is ...

Page 50: ...0m 65 230 22 15 15 86 70 35 27 1 5 h o l e 40 80 40 27 18 Fixing screw hole 4 5 5 95 220 22 35 120 12 30 200 2 2 2 9 74 7 8 Fig 4 ON SW1 Levers No 1 6 can set the following addresses respectively with binary notations Address Toggle 32 No 6 ON 16 No 5 ON 8 No 4 ON 4 No 3 ON 2 No 2 ON 1 No 1 ON 10 9 8 7 6 5 4 3 2 1 ON 10 9 8 7 6 5 4 3 2 1 ON 10 9 8 7 6 5 4 3 2 1 ON 10 9 8 7 6 5 4 3 2 1 Ex 1 3 2 1 E...

Page 51: ......

Page 52: ...O CCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO LTD Issued in Jul 2000 No OC155 REVISED EDITION B 1540 Issued in Dec 1997 No OC155 REVISED EDITION A 670 Issued in Sep 1997 No OC155 860 Printed in Japan New publication effective Jul 2000 Specifications subject to change without notice ...

Reviews: