Mitsubishi Electric PAR-30MAA User Manual Download Page 1

UserGuide

Controls

PAR-30MAA

BackUpandRotate

PAR-30MAA Back Up and Rotate

Select the 

Main menu 

by pressing

In the main menu screen move the
cursor using 

F1/F2

to 

Service

option and press

F1

F2

1.

Move the cursor next to the 

Check

option and press  

3.

Then select 

Request code

and press  

4.

In the Request code screen enter
the 

outdoor unit address

and the 

appropriate

rotation setting

see list on reverse. 

Outdoor unit address is the same 
as the refrigerant address.

5.

Enter 

maintenance password

(default is 9999)  

2.

Repeat step 5

for the slave unit as

both ref addresses (both outdoor
units) need a code request in order
for back up and rotate to operate.

Reviews: