RH79A029K01 

MITSUBISHI 

Mitsubishi Package Air Conditioner Optional Equipment 

Model PAC-SK01DM-EJ

..._ ELECTRIC 

Drain Pump Installation Manual 

LPK-L type 

• The Drain Pump should be installed on the wall next to the left side of the indoor unit for use.

• By installation of the Drain Pump, it is possible to run the drain tube and refrigerant tube together vertically.

• The Drain Pump should be installed after the indoor unit is positioned on the wall.

* Be sure to carefully read this manual and the installation manual for the indoor unit first before installation of the Drain Pump.

(  THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY  ) 

• Be sure to read "THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY" before installation.

• Be sure to observe the warnings and cautions specified here as they include important items related to safety.

• Precautions are classified as follows, according to the level of potential danger.

'&WARNING 

Denotes a condition or operation which, if handled incorrectly, may lead to serious injury or death.

&CAUTION 

Denotes a condition or operation which, if handled incorrectly, may lead to bodily injury or property damage.

• After installation work has been completed, explain the" THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY ", use,

and maintenance of the unit to the customer and perform the test run to ensure normal operation.

• Both the installation manual and operation manual must be given to the user for keeping.

These manuals must be passed on to subsequent users.

Do not alter the unit. 

WARNING 

It may cause fire, electric shock, injury or water leakage. 

Ask a dealer or an authorized technician to install the unit.  l 

If the unit is installed incorrectly, water leakage, electric 

,WARNING 

shock, or fire may result. 

,r 

For installation work, follow the instructions in the 

installation manual. 

WARNING 

If the unit is installed incorrectly, water leakage, electric 

shock, or fire may result. 

The unit must be securely installed on a structure that 

can sustain its weight. 

WARNING 

If the structure does not have sufficient strength, accidents 

may result due to falling of the unit. 

_/ 

l

Make sure that the refrigerant piping are well insulated  ' 

to prevent dew condensation. 

CAUTION 

Incomplete insulation may cause dew condensation on the surface 

of the pipes, wetting the ceiling, floor, and other important property. 

Make sure that the drainage piping is carried out 

correctly following the installation manual and that it 

is insulated in order to prevent dew condensation. 

CAUTION 

Any deficiency caused by piping may result in water leakage, 

wetting the ceiling, floor, and other personal property. 

The indoor unit must be installed horizontally. 

CAUTION 

Otherwise, the water can leak and it will make the wall dirty. 

1. Accessories 

(Make sure of the following items attached with the Drain Pump before installation.)

(A) Drain Pump  (B) Screw

(C) Screw

(D) Drain hose  (E) Flexible hose cover  (F) Band

(G) Paper gauge

@x1 

� 

<::J> 

(4 

35) 

(4x16)x1 

1

x2 

* The items (B) - (F) are packed between main body and exterior cover of the Drain Pump. Take them out after the exterior cover removed.

2. Overall dimensions and required installation space (mm)

Cutout hole for piping 

VP-20 pipe 

(Local procurement) 

C""I 

Flexible hose 

(VP20) port 

!  !'Refrigerant piping 

r-----ri;==�#-=l!i  (Two pipes can be raised 

Li 

together) 

"' 

N

a, 

� 

t·-1 

______ �-�-,  1 

*Except for water refrigerant 

• 

•  1 

indoor unit. 

!

!  i

!  .

-�·-·-·-·-· .. ·��-: 3

288 

Hole for Indoor 

unit piping 

Required space for installation of Drain Pump 

A *1 

E  F *2  G 

PK-L type  773/898 299 237 150  250  75  15 

*1 Refer to the installation manual of the indoor unit.

*2 In case that there is a rim at the corner of ceiling,

210 

consider the dimension of the rim before installation. 

Dimension of Mounting plate 

44 (Space for piping) 

Mounting 

plate 

120 

97 

..... 

Piping band position 

� 

N +---+-+- ·+--+-----+ 

�L--...::L----,1.._.../....,.,.J.,U���':""""/ 

� 

� 

6 - 05 dia. hole 

(For screw) 

,, 

(From indoor unit) 

350 or more  '-,_�! 

.  Drain Pum 

Paper gauge 

,  , 

,, 

ID 

-

1/ 

Dor more 

Fig.2 

Fig.3 

[I] 

3. Before installation of the Drain Pump 

(*  Position the indoor unit first.)

3-1 Set up of the Drain Pump

• Remove the exterior cover and the mounting plate which is fixed on the back of the Drain Pump.

* Take out the accessories.

• When installing the refrigerant piping vertically, run the band (F) attached through the square hole on the mounting plate,

and cut the cutout hole on the top of the exterior cover with a nipper.

Screws (2 pcs) 

Fig.4 

Mounting plate 

Screws (4 pcs) 

Main body of 

Drain Pump 

* The removed screws will be used later. Keep them not to lose.

Band (F) 

3-2 Set up and installation of the indoor unit 

(*See the item of piping connection set up in the installation manual of the indoor unit.) 

(1) Make the cutout hole for left side piping on the left side panel of the indoor unit.
(2) Pull out the drain cap from the left

rain 

(3) Remove the drain hose from the

drain outlet.

indoor unit.

• Hold the convex section at the

ap 

• Hold the end of the drain  hose (a)

end and pull the drain cap.

(marked by the arrow) and pull the

drain hose out (b).

Fig.5-1 

(5) Insert the accessory drain hose (D)

� 

Fig.5-2 

(4) Insert the drain cap into the

right drain outlet.

• Insert a screwdriver or similar

tool into the hole at the end of

the cap and insert the cap fully

into the outlet.

� 

cap 

Fig.5-3 

into the left drain outlet.

H�ok 

• Insert the hose up to the base of the

drain pipe connection opening.

* Make sure that the hook on the drain

hose is securely caught on the projection

in the opening in the drain pan.

(6) Install the indoor unit.

The indoor unit must be installed horizontally. 

CAUTION  1-----------------�------1

Otherwise, the water can leak and it will make the wall dirty. 

4. Installation of the Drain Pump

4-1  Fixing of the mounting plate

• The installation place should be carefully considered about whether

it is proper for installation. If it is not strong enough to hole the unit,

make it stronger by using board or beam before installation.

(1) Decide the installation position of the mounting plate by using the

paper gauge (G).

(* The left end of the indoor unit should be marked in advance.)

1) Fix the paper gauge (G) on the wall with the screw (C) (4 x 16)

attached with putting it to the left end of the indoor unit for

positioning of the Drain Pump as shown in the drawing.

2) Position the mounting plate with pushing it against the paper

gauge (G).

(2) Fix the mounting plate with the screws (B) (4 x 35) attached.

Fix the mounting plate using the 5 dia. holes.

(6 locations pointed by arrows in the drawing.)

In case that the mounting plate is fixed by fixing bolts (through

bolts, bolt anchors, or nut anchors), get M 10 or W3/8 screws locally

and put them into two 0 12 holes of the mounting plate to fix it.

(3) When the mounting plates is installed, remove the paper gauge (G).

(4) Check that the mounting plate is level and positioned correctly

with the indoor unit as shown in Fig.2.

Mounting plate 

Marking 

"' 

'

{) 

"' 

"' 

Align these 4 sides 

with the paper gauge (G). 

Fig.6 

Fig.5-4 

Indoor unit 

Paper gauge (G) 