background image

4

 Laying out the lead wire

5

 Removing the beam and the electrical box cover

6

 Connecting the receiver board connector to the control circuit board

3

 Installing to the indoor unit

2

 Removing the existing brand label case

RG79V986H01

Package Air-Conditioner

i-see Sensor                                                           PAC-SH91MK-E
Wireless remote controller kit with i-see Sensor   

 

PAR-SA92MW-E

Wireless remote controller kit                              PAR-SL93B-E

Installation Manual

 After using this manual, be sure to pass it to the customer together with the instruction manual provided with the indoor unit.

    Ask the customer to keep this installation manual and the instruction manual in a handy place, and to show them to the 
    engineer when the air-conditioner is moved or repaired. Also ask the customer to pass them to any new user.

Safety Precautions

 Read these “Safety Precautions” thoroughly and install securely.

 Precautions are classified using the following symbols depending on the extent and type of danger by erroneous handling.

WARNING
CAUTION

Erroneous handling can cause death or serious injury.
Erroneous handling can cause personal injury or damege.

This manual describes the installation for i-see sensor, wireless remote controller kit with i-see sensor and wireless remote 
controller kit of the Mitsubishi ceiling suspended series package air-conditioner. Read this manual carefully.

WARNING

 

Ask a dealer or specialist to install the unit.

 

Securely install the unit in a place that can with stand the

 weight.

• Otherwise, the unit could fall, which could cause injury.

 

Never modify the unit or repair it by yourself.
• Modification or incorrect repair could cause electric shock,
  fire, etc. Consult the dealer from whom you purchased 
  the unit.

 

Do not move the unit by yourself.

• Incomplete installation could cause electric shock, fire, 
  etc. Ask the dealer or a specialist for installation.

 

Securely install the unit, referring to this installation manual.
• Incomplete installation could cause electric shock, fire, 
  etc. 

All accessories must be installed by an anthorized technician.

• The user must not try to install accessories. Improperly
  installed accessories can cause water leakage, electric
  shock or fire. Shortage in electrical circuit capacity or 
  incomplete construction could cause fire, etc.

 

Securely connect the specified remote control cord, and 

 fix it so that the terminal connector is free from any external
 force via the cord.

• Incomplete connection or fixing could cause heat, fire, etc.

CAUTION

 

Do not install the unit in a place where flammable gas could leak.

• If gas leaks or accumulates around the unit, it could cause
  ignition, explosion, etc.

 

Do not use the unit in an abnormal environmaent.
• Usage in a place where there is much oil (including machine
  oil), steam, sulfide gas, etc. could greatly degrade its perfor-
  mance or damage components.

 

Do not install the unit in a bathroom, kitchen, etc. where a

 great amount of steam is generated.

• Avoid installing in a wall where condensation occurs. Insta-
  lling in such a place could cause a fault, electric shock, etc.

 

Do not install the unit in a place where acid solution, alkaline

 solution, special spray, etc. are frequently used.

• Installing in such a place could cause fault, electric shock, etc.

 

Take sufficient countermeasures against noise when the unit is installed in hospital, communication office, etc.

• This unit could malfunction when affected by inverter equipment, private electric generator, high-frequency medical instru-
  ments, radio communication devices, etc. Also, this unit could adversely affect medical instruments, communication devices,
  etc., thus interfering with human medical treatment, or causing disturbance in broadcast pictures or noise.

 

When doing wiring, make sure that wires are not subject 

 to tension.

• Tension on wires could disconnect them, or cause heat, fire, etc.

 

Do not rinse this unit with water.
• Doing so could cause fault, electric shock, etc.

 

Do not install the unit in a place where the ambient tem-

 perature is over 40°C or below 0°C, or exposed to direct
 sunlight.

• Installing in such a place could cause deformation, fault, etc.

 

Do not touch circuit boards with hands or  tools, or allow

 dust to adhere to them. 

• Failure to do so could cause fault, fire, etc.

 

Do not operate buttons with wet hands.

• Failure to do so could cause fault, electric shock, etc.

 

Do not push buttons with sharp objects.

• Failure to do so could cause fault, electric shock, etc.

Making Sure of Components

Make sure that the following components, along with this manual, are packed in the box.

Component


1

1
1
2
2
2
1

Wireless remote controller
Remote control holder
“AAA” LR03 alkaline batteries

4.1×16 wood screws

Cord retaining clips

Connection cord fixing seal (12×30 size)

How to Install

W

 Be sure to turn the power off before installing.

1

 Removing the intake grille and the right side panel

• Slide the catch holding the intake grille backwards to open the grille. Remove the screw holding the side panel,
  and then slide the side panel forward to remove it.

Side panel

Slide forward

Catch retaining the intake grille

Remove the screw holding the side panel

• Remove the brand label case (name plate with MITSUBISHI ELECTRIC) from the bottom right of the unit. If it is difficult 
  to remove the case, use a flat-blade screwdriver, etc., taking care not to damage the panel.

• Pass the lead wire through the right side of the square hole to which the brand label case was attached, and then pull 
  them thruogh the slit in the right side of the bottom panel.
• Fit the receiver or i-see sensor into the square hole where the brand label case was attached.

Lead wire 
(for i-see sensor)

Retaining clip

Slit

• Pass the lead wire through the retaining clips.
• Layout the lead wire along the vane motor lead wire, then fix them 
  with the clips on the ceiling side of the unit.

Retaining clip

Clips on the ceiling side 

• Remove the beam.
• Loosen the two screws at the bottom of the electrical box cover,
  and then slide the cover to the left to remove it.
• Pull down the electrical box.

{

 

Electrical box fixing screw 

   Electrical box cover fixing screw

Electrical box cover

Beam

<

W

only when wireless remote controller kit with i-see sensor PAR-SA92MW-E or wireless remote controller receiver 

    PAR-SL93B-E is used. >
• Pass the cord through the bush at the top right of the electrical box.
• Connect the connector to CN90 on the right of the control board.
• If  the cord is loose, bundle it using the clamps under the above bush.

CN6Y

CN4Y

CN90

Bush

Calmp

Calmp

Calmp

7

 Connecting the i-see sensor lead wire (radiation temp. sensor (black) and the stepping motor connector (transparent)) 

    to the control circuit board

<

W

only when wireless remote controller receiver PAC-SH91MK-E or wireless remote controller kit with i-see sensor 

    PAR-SA92MW-E is used. >
• Pass the cord through the bush at the top right of the electrical parts case.
• Connect the radiation temp. sensor (black) lead wire to CN4Y (white) on the control circuit board. 
• Connect the stepping motor (transparent) lead wire to CN6Y (red) on the control circuit board.

8

 Reinstalling the removed components

• Reinstall the removed components in reverse order. (The brand lavel case is not needed.)

Pair Number Setting

9

 Remote control holder

• To install the wireless remote controller on a wall, first attach the remote control holder to a wall.

1

3

2

Fitting remote control into holder

1

 Fix the remote control holder to the wall using 

    the 2 wood screws provided.

2

 Insert the remote control into the holder.

3

 Push the remote control against the wall.

Removing remote control

 Pull the top of remote control forward.

NOTE : The remote signal will reach the receiver over a distance of approx. 7m (23 ft.) in a straight line and 
             approx. 45° left or right. If the infrared receiver is affected by fluorescent light (especially, inverter type), 
             it may not be able to receive the signal. Take this into consideration when installing fluorescent lights or 
             replacing them. 

• This is  the setting to specify the unit to operate with the wireless remote controller.
• Make setting for J41, J42 (Jumper wire) of indoor controller board and the pair number of wireless remote cotroller.
• The pair number setting is available with the 4 patterns as shown in the following table. Make setting for the pair number 
  (J41, J42) of indoor controller board and the pair number of wireless remote controller which is used
  as shown in the following table. *The initial setting is Pair No. “0”.

1

 Press the SET button with something sharp at the end.

    Start this operation from the status of remote controller display turned off.

    

MODEL SELECT

 blinks and Model No. is lighted.

2

 Press the        button twice continuously. Pair No. “0” blinks.

3

 Press the temp            button to set the pair number you want to set.

4

 Press the SET button with something sharp at the end.

    Set pair number is lighted for 3 seconds then turned off.

A

 Pair No. of wireless remote controller Indoor PC board

Initial setting
  Cut J41
  Cut J42 
Cut J41, J42

0
1
2

  3 ~ 9

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL

SELECT

NOT AVAILABLE

SWING

CHECK

FAN

TEST

RUN

°F

°C

AMPM

STOP

START AMPM

COOL

DRY

AUTO

FAN

HEAT

1

 

4

1

 

4

2

 

3

3

CN6Y CN4Y CN90

Function Selection of Wireless Remote Controller

5

• Temperature display °C/°F setting (Change of temp mode from °F to °C)

1

 Press the set button with something sharp at the end. 

MODEL SELECT

 blinks. 

2

 Press the         button.  “F:” blinks.

3

 Press the       button. “C:” blinks.

4

 Press the SET button with something sharp at the end.

    

MODEL SELECT

 is lighted for three seconds, then turned off.

AUTO START

min

Jumper wire (J41, J42)

Panel 

Panel 

Case

Panel 

Slide 

Slide 

Slide 

• Incomplete installation could cause electric shock, fire, 
  etc. 

PAR-SA92MW-E

PAR-SL93B-E

PAC-SH91MK-E



1
1
1
2
2
2
1

1







Also on the 
opposite side

ON/OFF

TEMP

FAN

VANE

MODE

CHECK

LOUVER

TEST RUN

    AUTO STOP

     AUTO START

h

min

RESET

SET

CLOCK

MODEL SELECT

A

3

2

1

 

4

2

(Q’ty)

i-see sensor
Wireless remote controller receiver with i-see sensor
Wireless remote controller reciever 

Lead wire 
(for receiver)

* The positions of the connectors may be different according to the model.
  Please refer to the wiring diagram to confirm the positions of the connectors.

* The positions of the connectors may be different according to the model.
  Please refer to the wiring diagram to confirm the positions of the connectors.

Reviews: