6 INSTALLATION AND WIRING
6.5 Wiring of Terminal Block for Module Power Supply and FG
127
6
6.5
Wiring of Terminal Block for Module Power Supply
and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screws too much may damage the case of I/O module (except for waterproof module).
Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screws with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Screw type
Tightening torque range
Terminal block mounting screw (M2.5 screw)
0.2 to 0.3 N
m
Diameter
Type
Material
Temperature rating
22 to 16 AWG
Stranded
Copper
75
or more
Product
name
Terminal shape
Model
Applicable wire
size
Bar solderless
terminal tool
Contact
Bar solderless
terminal
Ferrule (with insulation
sleeve)
TE0.5-8, TE0.5-10
0.3 to 0.5
NH-79A
NICHIFU Co., Ltd.
TE0.75-8, TE0.75-10
0.75
AI0.34-10TQ
0.34
CRIMPFOX6
PHOENIX CONTACT GmbH &
Co. KG
AI0.5-10WH
0.5
AI0.75-10GY
0.75
Ferrule (without
insulation sleeve)
A0.5-10
0.5
A0.75-10
0.75
A1.0-10
1.0
A1.5-10
1.5
Summary of Contents for NZ2GN2B1-32D
Page 2: ......
Page 112: ...110 4 PROCEDURES BEFORE OPERATION MEMO ...
Page 193: ...10 MAINTENANCE AND INSPECTION 191 10 MEMO ...
Page 263: ...I 261 MEMO ...
Page 267: ......