120
6 INSTALLATION AND WIRING
6.2 Setting Switch
Function setting switch setting
Set the following functions using the function setting switch on the front of I/O module.
• Network setting function
• Input response time setting function
• Output HOLD/CLEAR setting function
• CC-Link IE TSN Network synchronous communication function
• Communication speed setting function
The setting of function setting switch is enabled when the I/O module is powered on. Thus, set each function when the module
is powered off.
When operating the function setting switch, use a flathead screwdriver having a blade of 1.2mm or less in
width.
Setting procedure
Set each function with function setting switch 1 to function setting switch 10.
Do not change any function setting switch while the I/O module is powered on. If the setting of a function
setting switch is changed while the I/O module is powered on, one of the errors from Function setting switch 1
changed error (error code: 0201H) to Function setting switch 10 changed error (error code: 020AH) occurs,
and the changed setting of that function setting switch is not applied. Returning the function setting switch to
its previous position and turning on Error clear request flag (RWw0.b10) eliminate the error.
Switch name
Function name
Setting details
Function setting switch 1
NETWORK
Network setting function
Set this switch to OFF in normal operation.
Set it to ON to perform a unit test. (
Function setting switch 2 to function
setting switch 4
RESPONSE
Input response time setting
function
Set the input response time. (
Function setting switch 5
HOLD/CLEAR
Output HOLD/CLEAR setting
function
Set output HOLD/CLEAR. (
Function setting switch 6, function
setting switch 7
MODE
CC-Link IE TSN Network
synchronous communication
function
■
For the I/O module with the firmware version of "05" or later
Set the CC-Link IE TSN Network synchronous communication.
(
Page 174 Operation mode setting)
■
For the I/O module with the firmware version of "04" or earlier
Fix these switches to OFF.
Function setting switch 8, function
setting switch 9
F LINK P1/P2
Use prohibited
Fix these switches to OFF.
Function setting switch 10
LINK SPEED
Communication speed
setting function
■
For the I/O module with the firmware version of "02" or later
Set the communication speed. (
■
For the I/O module with the firmware version of "01"
Fix this switch to OFF.
Summary of Contents for NZ2GN2B1-32D
Page 2: ......
Page 112: ...110 4 PROCEDURES BEFORE OPERATION MEMO ...
Page 193: ...10 MAINTENANCE AND INSPECTION 191 10 MEMO ...
Page 263: ...I 261 MEMO ...
Page 267: ......