178
(8) Setting the number of alert delay
Set the number of sampling to judge alert occurrence. The system is set in the alert status when the temperature
process value (PV) that has reached the alert set value remains in the alert range until the number of sampling
becomes equal to or greater than the preset number of alert delays.
(a) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "Warning delay count".
Ex.
When the alert mode is set to "1: Upper limit input alert" (
When 5 is set as the number of alert delay, the system is not put in the alert status if the number of
sampling is 4 or less.
Non-alert status
Alert status
Time
Temperature process value (PV)
Alert status
Number of sampling
Alert set value
3 times
5 times
Set value (SV)