The performance specifications of each part of the Ethernet adapter module are described below.
(1) Power supply part
Item
Specification
Input voltage (
Page 32, Section 3.2.1 (1) (a))
24VDC (-35% to +30%)
Current consumption
0.6A
Inrush current (
Page 32, Section 3.2.1 (1) (b)) 100A, 1ms or less
Allowable momentary power failure time (
Page 32, Section 3.2.1 (1) (c))
10ms or less
Withstand voltage
510V AC/min (Altitude: 0 to 2000m)
Between the combined "line input/LG terminals" and the "FG terminal and output"
Insulation resistance
10M
or higher by 500VDC insulation resistance tester
Between the combined "line input/LG terminals" and the "FG terminal and output", the
line input and LG terminals, the output and FG terminals
Noise immunity
• By noise simulator of 500Vp-p noise voltage, 1
s noise width, and 25 to 60 Hz
noise frequency
• Noise voltage IEC 61000-4-4, 2kV
Operation status indicator
LEDs (Normal: On (green), Error: Off)
Fuse
Built-in (not replaceable)
Terminal screw size
M3.5
Applicable wire size
0.75 to 2 mm
2
Applicable solderless terminal
RAV1.25-3.5, RAV2-3.5, 0.8mm or less in thickness, Two solderless terminals can be
connected to one terminal.
Applicable tightening torque
0.66 to 0.89N
m
Power supply part
Ethernet part
CC-Link IE
Field Network part
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......