178
(5) Error code list (E000
H
to FFFF
H
)
The following lists the error messages, error conditions, causes, and actions of the error codes (E000
H
to
FFFF
H
).
D911
H
Destination IP address error
Check the destination IP address of the IP communication test.
DA00
H
to DA01
H
Ethernet adapter module failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
DA10
H
to DA18
H
Ethernet adapter module failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
DAF2
H
Failed to write to flash ROM
• If the number of times that data were written to the flash ROM exceeded
100,000, set the system not to hold the error history by power-off/reset in
"PLC System" in the parameter setting.
• Check the wire and cable distances and grounding condition of each
device, and take measures against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
DAF3
H
MAC address read error
• The RAM may malfunction due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
Error code
Error
Action
E000
H
to EFFF
H
Errors that may be detected by the
CC-Link IE Controller Network
Refer to the CC-Link IE Controller Network reference manual.
F000
H
to FFFF
H
Errors that may be detected by the
MELSECNET/H or MELSECNET/10
network system
Refer to the MELSECNET/H or MELSECNET/10 network system reference
manual.
Error code
Error
Action
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......