Appendix 4
I/O Conversion Characteristics of D/A
Conversion
The I/O conversion characteristics of D/A conversion are expressed by the slope of the straight line connecting the
offset value and the gain value, both of which are used when a digital value written from the CPU module is converted
to the corresponding analog output value (voltage or current output).
(1) Offset value
An analog output value (voltage or current) corresponding to the digital value 0 under the condition that the
scaling function and the shift function are not used.
(2) Gain value
An analog output value (voltage or current) corresponding to the following digital value under the condition that
the scaling function and the shift function are not used.
• 12000 (When the output range is set to 0 to 5V, 1 to 5V, 0 to 20mA, 4 to 20mA, user range setting 1, or user
range setting 2)
• 16000 (When the output range is set to -10 to 10V)