11-5. TROUBLE CRITERION OF MAIN PARTS
MXZ-3C24NA MXZ-3C30NA MXZ-4C36NA MXZ-5C42NA
MXZ-2C20NAHZ MXZ-3C24NAHZ MXZ-3C30NAHZ
MXZ-3C24NA2 MXZ-3C30NA2 MXZ-4C36NA2 MXZ-5C42NA2
MXZ-2C20NAHZ2 MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
W
U
V
WHT
RED
BLK
LEV
WHT
RED
YLW
ORN
BLU
Linear expansion valve
37.4
- 53.9
Normal
Color of lead wire
WHT - RED
RED - ORN
YLW - RED
RED - BLU
High pressure switch
(HPS)
Pressure
Normal
HPS
537 ± 22 PSIG
696 PSIG
Open
Close
+ 7
-
15
Discharge temperature
thermistor (RT62)
Measure the resistance using a tester. (Part temperature: 14°F - 104°F)
Measure the resistance using a tester. (Part temperature: 14°F - 104°F)
Part name
Check method and criterion
Measure the resistance between terminals using a tester.
(Winding temperature: 14°F - 104°F)
Compressor
Outdoor fan motor
R.V. coil
Defrost thermistor (RT61)
Fin temperature
thermistor (RT64)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor (RT68)
Measure the resistance with a tester.
Refer to 11-7. “Test point diagram and voltage”, 1. ”Outdoor control P.C.board”,
2. ”Outdoor power P.C. board”, for the chart of thermistor.
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-7. “Test point diagram and voltage”,1. ”Outdoor control P.C. board” for the chart of thermistor.
MXZ-3C24NA MXZ-3C30NA MXZ-4C36NA
MXZ-3C24NA2 MXZ-3C30NA2 MXZ-4C36NA2
MXZ-3C24NA MXZ-3C30NA MXZ-4C36NA
MXZ-3C24NA2 MXZ-3C30NA2 MXZ-4C36NA2
Normal (Each phase)
NN
Normal (Each phase)
Measure the resistance between terminals using a tester.
(Winding temperature: 14°F - 104°F)
MXZ-5C42NA MXZ-2C20NAHZ MXZ-3C24NAHZ MXZ-3C30NAHZ
MXZ-5C42NA2 MXZ-2C20NAHZ2 MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
MXZ-5C42NA MXZ-2C20NAHZ MXZ-3C24NAHZ MXZ-3C30NAHZ
MXZ-5C42NA2 MXZ-2C20NAHZ2 MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
Normal (Each phase)
NN
Normal (Each phase)
5HIHUWR
Normal
Measure the resistance using a tester. (Part temperature: 14°F - 104°F)
2-way valve solenoid coil
MXZ-5C42NA
MXZ-2C20NAHZ
MXZ-3C24NAHZ
MXZ-3C30NAHZ
MXZ-5C42NA2
MXZ-2C20NAHZ2
MXZ-3C24NAHZ2
MXZ-3C30NAHZ2
Measure the resistance using a tester. (Part temperature: 14°F - 104°F)
NN
MXZ-5C42NA
MXZ-2C20NAHZ
MXZ-3C24NAHZ
MXZ-3C30NAHZ
MXZ-5C42NA2
MXZ-2C20NAHZ2
MXZ-3C24NAHZ2
MXZ-3C30NAHZ2
Normal
Measure the resistance using a tester. (Part temperature: 14°F - 104°F)
Defrost heater
MXZ-2C20NAHZ
MXZ-3C24NAHZ
MXZ-3C30NAHZ
MXZ-2C20NAHZ2
MXZ-3C24NAHZ2
MXZ-3C30NAHZ2
0.35
N
- 0.50
N
OBH702E
Summary of Contents for MXZ-2C20NAHZ
Page 17: ...17 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702E ...
Page 19: ...19 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702E ...
Page 21: ...21 MXZ 3C24NA MXZ 3C30NA WIRING DIAGRAM 6 OBH702E ...
Page 22: ...22 MXZ 3C24NA2 MXZ 3C30NA2 OBH702E ...
Page 23: ...23 MXZ 4C36NA OBH702E ...
Page 24: ...24 MXZ 4C36NA2 OBH702E ...
Page 26: ...26 MXZ 5C42NA2 OBH702E ...
Page 27: ...27 MXZ 2C20NAHZ OBH702E ...
Page 28: ...28 MXZ 2C20NAHZ2 OBH702E ...
Page 29: ...29 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702E ...