70
3. Table of outdoor unit failure mode recall function
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition
Remedy
Indoor/
outdoor unit
failure mode
recall function
LED 1
LED 2
OFF
None (Normal)
Lighted Lighted
2-time fl ash
Outdoor power system
Lighted Lighted Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started, or converter
protection cut-out or bus-bar voltage
protection cut-out operates 3 consecutive
times within 3 minutes after startup.
• Check the connection of the com-
pressor connecting wire.
• Refer to 11-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
○
3-time fl ash
Discharge temperature thermistor Lighted
Once
A thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of outdoor
thermistors".
○
Defrost thermistor
Lighted
Once
Ambient temperature thermistor
Lighted
Twice
Fin temperature thermistor
Lighted 3 times
P.C. board temperature thermistor Lighted 4 times
• Replace the outdoor control P.C. board.
Outdoor heat exchanger tem-
perature thermistor
Lighted 9 times
• Refer to 11-6. "Check of outdoor
thermistors".
4-time fl ash
Overcurrent
Once
Not
lighted
21 A (
MXZ-3C24/3C30/4C36NA, MXZ-3C24/
3C30/4C36NA2
)/28 A (
MXZ-5C42NA, MXZ-
2C20/3C24/3C30NAHZ, MXZ-5C42NA2,
MXZ-2C20/3C24/3C30NAHZ2
) current flows
into power module.
• Reconnect compressor connector.
• Refer to 11-6. "How to check in-
verter/compressor".
• Check the stop valve.
—
5-time fl ash
Discharge temperature
Lighted Lighted The discharge temperature exceeds 222.8°F
(
MXZ-3C24/3C30/4C36NA, MXZ-3C24/3C30/
4C36NA2
)/240.8°F (
MXZ-2C20/3C24/3C30
NAHZ, 5C42NA, MXZ-2C20/3C24/3C30
NAHZ2, 5C42NA2
) during operation.
Compressor can restart if discharge tempera-
ture thermistor reads 203°F (
MXZ-3C24/3C30
/4C36NA, MXZ-3C24/3C30/4C36NA2
)/212°F
(
MXZ-2C20/3C24/3C30NAHZ, 5C42NA,
MXZ-2C20/3C24/3C30NAHZ2, 5C42NA2
) or
less 3 minutes later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
6-time fl ash
High pressure
Lighted Lighted The outdoor heat exchanger temperature ex-
ceeds 158°F during cooling or the indoor gas
pipe temperature exceeds 158°F during heating.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
—
7-time fl ash
Fin temperature
3 times
Not
lighted
The fin temperature exceeds 190°F (
MXZ-
3C24/3C30/4C36NA, MXZ-3C24/3C30/
4C36NA2
)/192°F (
MXZ-2C20/3C24/
3C30NAHZ, 5C42NA, MXZ-2C20/3C24/3C30
NAHZ2, 5C42NA2
) during operation.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-6. "Check of outdoor
fan motor".
—
P.C. board temperature
4 times
Not
lighted
The P.C. board temperature exceeds 152°F
(
MXZ-3C24/3C30/4C36NA, MXZ-3C24/3C30/
4C36NA2
)/189°F (
MXZ-2C20/3C24/3C30
NAHZ, 5C42NA, MXZ-2C20/3C24/3C30
NAHZ2, 5C42NA2
) during operation.
8-time fl ash
Outdoor fan motor
Lighted Lighted A failure occurs 3 consecutive times within
30 seconds after the fan gets started.
• Refer to 11-6. "Check of outdoor
fan motor".
—
9-time fl ash
Outdoor control system
Lighted 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor control P.C.
board.
○
10-time fl ash
Low discharge temperature
protection
Lighted Lighted The frequency of the compressor is kept 80
Hz or more and the discharge temperature is
kept under 102.2°F for more than 20 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
11-time fl ash
Communication error
between P.C. boards
Lighted 6 times Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
—
The communication between boards protec-
tion cut-out operates 2 consecutive times.
○
Current sensor
Lighted 7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
—
—
Current sensor protection cut-out oper-
ates 2 consecutive times.
○
Zero cross detecting circuit
5 times
Not
lighted
Zero cross signal cannot be detected
while the compressor is operating.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
—
The protection cut-out of the zero cross de-
tecting circuit operates 10 consecutive times.
○
Converter
5 times
Not
lighted
A failure is detected in the operation of the
converter during operation.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
—
Bus-bar voltage
6 times
Not
lighted
The bus-bar voltage exceeds 400 V or
falls to low level during compressor oper-
ating.
• Check the voltage of power supply.
• Replace the outdoor control P.C.
board.
15-time fl ash
LEV and drain pump
Lighted Lighted The indoor unit detects an abnormality in
the LEV and drain pump.
• Refer to 11-6. "Check of LEV".
• Check the drain pump of the indoor unit.
—
NOTE
: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (11-4.).
OBH702E
Summary of Contents for MXZ-2C20NAHZ
Page 17: ...17 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702E ...
Page 19: ...19 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702E ...
Page 21: ...21 MXZ 3C24NA MXZ 3C30NA WIRING DIAGRAM 6 OBH702E ...
Page 22: ...22 MXZ 3C24NA2 MXZ 3C30NA2 OBH702E ...
Page 23: ...23 MXZ 4C36NA OBH702E ...
Page 24: ...24 MXZ 4C36NA2 OBH702E ...
Page 26: ...26 MXZ 5C42NA2 OBH702E ...
Page 27: ...27 MXZ 2C20NAHZ OBH702E ...
Page 28: ...28 MXZ 2C20NAHZ2 OBH702E ...
Page 29: ...29 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702E ...