40
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables
below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Piping length each indoor unit (a, b, c)
82 ft. MAX.
Total piping length (a+b+c)
230 ft. MAX.
Bending point for each unit
25 MAX.
Total bending point
70 MAX.
It is irrelevant which unit is higher.
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ-3C24NAHZ MXZ-3C30NAHZ MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
Operating Range
MXZ-3C24NAHZ MXZ-3C30NAHZ MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
a
b
Outdoor
unit
Indoor
units
Max. height difference
49 ft.
49 ft.
c
49 ft.
Outdoor unit union diameter
For
Indoor unit A
Liquid
1/4
Gas
1/2
Indoor unit B
Liquid
1/4
Gas
3/8
Indoor unit C
Liquid
1/4
Gas
3/8
Indoor intake air temperature
Outdoor intake air temperature
Cooling
Maximum
95°FDB, 71°FWB
115°FDB
Minimum
67°FDB, 57°FWB
14°FDB
Heating
Maximum
80°FDB, 67°FWB
75°FDB, 65°FWB
Minimum
70°FDB, 60°FWB
-12°FDB, -13°FWB
OBH702E
Summary of Contents for MXZ-2C20NAHZ
Page 17: ...17 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702E ...
Page 19: ...19 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702E ...
Page 21: ...21 MXZ 3C24NA MXZ 3C30NA WIRING DIAGRAM 6 OBH702E ...
Page 22: ...22 MXZ 3C24NA2 MXZ 3C30NA2 OBH702E ...
Page 23: ...23 MXZ 4C36NA OBH702E ...
Page 24: ...24 MXZ 4C36NA2 OBH702E ...
Page 26: ...26 MXZ 5C42NA2 OBH702E ...
Page 27: ...27 MXZ 2C20NAHZ OBH702E ...
Page 28: ...28 MXZ 2C20NAHZ2 OBH702E ...
Page 29: ...29 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702E ...