30
9-3. TROUBLE CRITERION OF MAIN PARTS
MU-GF20VA MU-GF25VA MU-GF35VA MU-GF50VA MU-GF60VA MU-GF80VA
Part name
Check method and criterion
Figure
Compressor
INNER
PROTECTOR
MU-GF20/60VA
150 ± 5°C OPEN
90 ± 10°C CLOSE
MU-GF25/50/80VA
160 ± 5°C OPEN
90 ± 10°C CLOSE
MU-GF35/50VA
155 ± 5°C OPEN
90 ± 10°C CLOSE
Measure the resistance between terminals using a tester.
(Temperature: -10 ~ 40°C)
Normal (Ω)
MU-GF20VA
MU-GF25VA
MU-GF35VA
C-R
3.98 ~ 4.88
3.19 ~ 3.91
2.37 ~ 2.91
C-S
6.23 ~ 7.63
4.76 ~ 5.83
3.09 ~ 3.79
Normal (Ω)
MU-GF50VA
MU-GF60VA
MU-GF80VA
C-R
1.87 ~ 2.29
0.83 ~ 1.03
0.59 ~ 0.74
C-S
2.99 ~ 3.67
1.30 ~ 1.60
1.58 ~ 1.95
Outdoor fan motor
INNER FUSE
MU-GF20/25VA
130°C CUT OFF
MU-GF35/50VA
145°C CUT OFF
INNER PROTECTOR
MU-GF60VA
130 ± 5°C OPEN
83 ± 15°C CLOSE
MU-GF80VA
145 ± 5°C OPEN
94 ± 15°C CLOSE
Measure the resistance between lead wires using a tester.
(Temperature: -10 ~ 40°C)
Color of
lead wire
Normal (Ω)
MU-GF20VA MU-GF25VA MU-GF35/
50VA
MU-GF60VA MU-GF80VA
WHT – BLK
243 ~ 298
150 ~ 185 63 ~ 78
56 ~ 70
BLK – RED
205 ~ 252
199 ~ 244 78 ~ 97
74 ~ 91
: INNER PROTECTOR
P
C
S
R
RED
WHT
BLK
WHT
RED
BLK
AUX.
MAIN
FUSE
MU-GF20/25/35/50VA
MAIN
AUX.
WHT
BLK RED ORN
MU-GF60/80VA
OBH622A