<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector
CNM on outdoor controller board.
F5
—
—
—
E6
E7
—
—
E0
E3
E4
E5
EF
Ed
A0~A8
[Display]
(1)Normal condition
(2)Abnormal condition
Unit condition
Outdoor controller board
A-Control Service Tool
LED1 (Green)
LED2 (Red)
Error code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
Lighted
Lighted
Lighted
Lighted
Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc.
08, etc.
C5, H7 etc.
Indication
Error
Error
code
+
1
Outdoor controller board
Contents
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector (63H) is open.
Startup time over
Error code is not defined.
Miswiring of indoor/outdoor unit
connecting wire, excessive number of
indoor units (4 units or more)
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or
disconnection)
Indoor/outdoor unit communication
error (signal receiving error) is
detected by indoor unit.
Indoor/outdoor unit communication
error (transmitting error) is
detected by indoorunit.
Indoor/outdoor unit communication
error (signal receiving error) is
detected by outdoor unit.
Indoor/outdoor unit communication
error (transmitting error) is
detected by outdoor unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
<Communication between outdoor
controller board and M-NET P.C. board>
Communication error of M-NET
system
1.Error code displayed on remote controller
2.Refer to service manual for indoor unit.
Check if indoor/outdoor connecting wire is connected correctly.
Check if 4 or more indoor units are connected to outdoor unit.
Check if noise entered into indoor/outdoor connecting wire
or power supply.
Re-check error by turning off power, and on again.
Check if connector (63H) on the outdoor controller board
is not disconnected.
Check continuity of pressure switch (63H) by tester.
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
Check if there is poor connection of connector on outdoor
controller board(CNMNT and CNVMNT).
Check M-NET communication signal.
Check if remote controller is MA remote controller (PAR-21MAA).
Check if noise entered into transmission wire of remote controller.
Check if noise entered into indoor/outdoor connecting wire.
Re-check error by turning off power, and on again.
Check if connecting wire of indoor unit or remote controller
is connected correctly.
Check if noise entered into transmission wire of remote
controller.
Re-check error by turning off power, and on again.
Check if indoor/outdoor connecting wire is connected correctly.
Check if noise entered into indoor/outdoor connecting wire or
power supply.
Check if noise entered into indoor/outdoor controller board.
Re-check error by turning off power, and on again.
P.27
P.28
(EA)
P.28
(Eb)
P.28
(EC)
+
2
+
2
P.33
(E8)
P.33
(E9)
P.32
P.32
P.32
P.32
P.33
P.33
P.34~
P.37
Detailed
reference
page
OCH512