78
10-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode.
Change the setting when needed.
Item 1
1.Change language
("CHANGE LANGUAGE")
2.Function limit
("FUNCTION SELECTION")
3.Mode selection
("MODE SELECTION")
4.Display change
("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller
* When 2 remote controllers are connected to 1 group, 1 controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (
or
°
F) to display
• Setting the use or non-use of the display of indoor (room) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display
during operation with automatic mode
Item 2
Language setting to display
(1) Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2) Use of automatic mode setting ("SELECT AUTO MODE")
(3) Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1) Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK")
(3) Timer function setting ("WEEKLY TIMER")
(4) Contact number setting for error situation ("CALL.")
(1) Temperature display
/°F setting ("TEMP MODE
/
°
F")
(2) Room air temperature display setting ("ROOM TEMP DISP SELECT")
(3) Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page.
[1] Stop the air conditioner to start remote controller function selection mode.
[2] Select from item1.
[3] Select from item2.
[4] Make the setting.
(Details are specified in item3) [5] Setting completed.
[6] Change the display to the normal one. (End)
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
•
Press the [
MENU] button to change the language.
Japanese (JP),
English (GB),
German (D),
Spanish (E),
Russian (RU),
Italian (I),
Chinese (CH),
French (F)
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
•
To switch the setting, press the [ ON/OFF] button.
no1 : All operation buttons except [ ON/OFF] button are locked.
no2 : All operation buttons are locked.
OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER]
and [ ON/OFF] buttons at the same time for 2 seconds.) on
the normal screen after the above setting is made.
.
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has auto-
matic operation mode, the following settings can be made.
•
To switch the setting, press the [ ON/OFF] button.
ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
OFF
: The automatic mode is not displayed
when the operation mode is selected.
[4] -3. Mode selection setting
(1) Remote controller main/sub setting
•
To switch the setting, press the [
ON/OFF] button.
Main : The controller will be the main controller.
Sub : The controller will be the sub controller.
(2) Use of clock setting
•
To switch the setting, press the [
ON/OFF] button.
ON : The clock function can be used.
OFF: The clock function cannot be used.
(3) Timer function setting
•
To switch the setting, press the [
ON/OFF] button. (Choose
one of the followings.)
WEEKLY TIMER (initial setting):
The weekly timer can be used.
AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER:
The simple timer can be used.
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER"
cannot be used.
(4) Contact number setting for error situation
•
To switch the setting, press the [
ON/OFF] button.
CALL OFF : The set contact numbers are not displayed in case
of error.
CALL **** *** **** : The set contact numbers are displayed
in case of error.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the
set range.
•
To switch the setting, press the [ ON/OFF] button.
LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.
OFF (initial setting) : The temperature range limit is not active.
* When the setting, other than OFF, is made, the temperature range limit setting
on cooling, heating and automatic mode is made at the same time. However
the range cannot be limited when the set temperature range has not changed.
•
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
•
To switch the upper limit setting and the lower limit setting, press the [ ]
button. The selected setting will flash and the temperature can be set.
•
Settable range
Cooling/Dry mode : Lower limit: 19
~ 30
Upper limit: 30
~ 19
Heating mode :
Lower limit: 17
~ 28
Upper limit: 28
~ 17
Automatic mode :
Lower limit: 19
~ 28
Upper limit: 28
~ 19
CALL_
: The contact number can be set when the display
is as shown on the left.
•
Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [
TEMP. (
) and
(
)] button to move the cursor to the right (left). Press the [
CLOCK
(
) and ( )] button to set the numbers.
[4] -4. Display change setting
(1) Temperature display
/ °F setting
•
To switch the setting, press the [
ON/OFF] button.
: The temperature unit
is used.
°F : The temperature unit °F is used.
•
To switch the setting, press the [
ON/OFF] button.
(3) Automatic cooling/heating display setting
•
To switch the setting, press the [
ON/OFF] button.
ON : One of "Automatic cooling" and "Automatic heating" is
displayed under the automatic mode is running.
OFF: Only "Automatic" is displayed under the automatic mode.
(2) Room air temperature display setting
ON : The room air temperature is displayed.
OFF : The room air temperature is not displayed.
OCH526