14
Cooling
Heating
47,800
54,600
14,000 (6,200~15,300)
14,000 (5,500~15,300)
16,000 (6,200~18,000)
16,000 (5,000~18,000)
4.99
4.91
PLA-RP6AA.UK
PLA-RP6AA
1
.UK
Single phase, 50Hz, 220-230-240V
0.33
0.33
1.64
1.64
2.0
2.0
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct)
o
1
0.120
22-25-28-30 (775-880-990-1,060)
0 (direct blow)
Remote controller & built-in
37-40-43-45
32 (1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4)
PANEL : 30 (1-3/16)
UNIT : 32 (71)
PANEL : 5 (11)
—
Service Ref.
Item
Function
Capacity
Btu/h
W
W
PUHZ-RP6VHA
PUHZ-RP6VHA
1
Total input
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
A
Starting current
A
External finish (Panel)
Heat exchanger
Fan
Fan (drive)
o
No.
Fan motor output
kW
kW
kW
Airflow
(Low-Medium2-Medium1-High)
K
/ min (CFM)
External static pressure
Pa (mmAq)
Booster heater
kW
Operation control & Thermostat
Sound level
(Low-Medium2-Medium1-High)
dB
Unit drain pipe I.D.
mm (in.)
Dimensions
Indoor unit
W
mm (in.)
D
mm (in.)
H
mm (in.)
Weight
kg (lbs.)
PLA-RP6AA.UK
PLA-RP6AA
1
.UK
PUHZ-RP6VHA
PUHZ-RP6VHA
1
Outdoor unit Service Ref.
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor: D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor: D.B. 35
:
(95˚F)
W.B. 24
:
(75˚F)
Heating : Indoor: D.B. 20
:
(68˚F)
Outdoor: D.B. 7
:
(45˚F)
W.B. 6
:
(43˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35
:
, W.B. 22.5
:
D.B. 46
:
Lower limit D.B. 19
:
, W.B. 15
:
D.B. -5
:
Heating
Upper limit D.B. 28
:
D.B. 21
:
, W.B. 15
:
Lower limit D.B. 17
:
D.B. -11
:
, W.B. -12
:
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
3. Guaranteed voltage
198~264V, 50Hz
5. Refer to the service manual of outdoor unit for tha outdoor
unit's specifications.