background image

Air-Conditioners
INDOOR UNIT

PEA-RP250 WHA

GB

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.

WT05750X01_cover.p65

09/9/15, 16:55

3

Summary of Contents for Mr.Slim PEA-RP250WHA

Page 1: ...Air Conditioners INDOOR UNIT PEA RP250 WHA GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Page 2: ...D Washers accessory E M10 hanging bolt field supply 5 5 3 Fig 5 1 1 Fig 5 1 2 Fig 5 3 1 5 1 6 6 2 Fig 6 2 1 A Indoor unit s bottom surface 701 494 235 1034 1324 A A B A C D C E D A Air inlet B Refrigerant piping liquid C Refrigerant piping gas D Control box E Drain pipe F Air outlet 165 52 100 244 30 424 A B E C D F Fig 4 1 1 Fig 3 2 1 A Access door B Electrical parts box C Air inlet D Air outlet ...

Page 3: ...en the insulation and the main body I Thermal insulation tubing small supplied 1 J Ties large supplied 4 K Ensure that there is no gap here Place join upwards L Thermal insulation tubing medium supplied 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here M M Q R P O N Fig 7 2 2 A Indoor unit B Insulation pipe short...

Page 4: ...g 8 0 1 B G E F H A I C C D D A Air inlet B Air filter supplied at site C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct work length 850 mm or more Fig 9 2 2 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L N C A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller ...

Page 5: ...th the transmis sion terminal 9 3 Fig 9 5 1 Fig 9 3 4 9 5 A Terminal bed box B Knockout hole C Remove Fig 9 3 1 Fig 9 3 2 B C A A B I J F G E L N 1 2 L S M2 M1 K H O N M L N M2 M1 M2 S M1 A B C D A Screw holding cover 2pcs B Cover SWA SW5 SW14 SW12 SW11 SWC Indoor controller board Fig 9 3 3 E Use PG bushing to keep the weight of the cable and external force from being applied to the power supply t...

Page 6: ...frigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being ...

Page 7: ...fied capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air conditioner units Washing them may cause an electric shock Be careful that the installation base is not damaged by long use If the damage is left uncorrected the unit may fall and cause personal injury or property damage Install the drain piping ac...

Page 8: ...pipes Insulate all indoor pipes with form polyethylene insulation with a minimum density of 0 03 and a thickness as specified in the table below 1 Select the thickness of insulating material by pipe size Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high...

Page 9: ...E Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supply H Insulating material field supply I Max 145 5 mm 7 Connecting refrigerant pipes and drain pipes 7 1 Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit For constraints on pipe length and allowable difference of elevation refer to the outdoor unit...

Page 10: ...rd not to touch the fan Fig 8 0 1 P 4 A Air inlet B Air filter supplied at site C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct work length 850 mm or more Table 1 Transmission cable length Less than 80 m Facility example for noise judgment Types of transmission cables Residence or independent store without noise VCTF VCTFK C...

Page 11: ...oller Shield wire connection Fig 9 3 4 P 5 A Terminal bed B Round terminal C Shield wire D Insulation tape To keep the earth wire of the shielded cable from coming in con tact with the transmission terminal 5 After wiring is complete make sure again that there is no slack on the connec tions and attach the cover onto the terminal bed box in the reverse order of removal Notes Do not pinch the cable...

Page 12: ...Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Reviews: