4-5. OPERATING RANGE
(1) POWER SUPPLY
Indoor unit
Outdoor unit
Rating
115V 60Hz 1
[
208/230V 60Hz 1
[
Guaranteed Voltage
MSH24WN
MUH24WN
Model
Min. 103V
Max. 127V
115V
Min. 198V
Max. 253V
208V 230V
(2) OPERATION
78%
—
Function
Cooling
Heating
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Standard temperature
Maximum temperature
Minimum temperature
DB (˚F)
80
95
67
70
80
70
WB (˚F)
67
71
57
60
67
60
Indoor
DB (˚F)
95
115
67
47
75
17
WB (˚F)
—
—
—
43
65
15
Outdoor
Condition
Intake air
temperature
4-6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
MSH24WN
Mode
HEAT
COOL
565
565
487
Air flow
(CFM)
Air speed
(ft./sec.)
Coverage
range (ft.)
Function
Dry
Dry
Wet
20.1
20.1
17.2
34.2
34.2
29.4
4-7. ADDITIONAL REFRIGERANT CHARGE (R22(oz.))
MSH24WN MUH24WN
Outdoor unit
precharged
(up to 25ft.)
4 lb. 0 oz.
25ft.
0
30ft.
1.61
35ft.
3.22
Refrigerant piping length (one way)
40ft.
4.83
45ft.
6.44
50ft.
8.05
Model
CALCULATION : Xoz. = 1.61/ 5oz./ft. x (Additional Piping Length-25) ft.
●
The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out
horizontally from the unit properly at the High speed position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture
arranged inside the room.