Job Name:
Location:
Date:
Purchaser: Engineer:
Submitted to:
For Reference Approval Construction
System Designation:
Schedule No.:
Cooling Capacity*
. . . . . . . . . . . . . . . . . . . . . . . . . . . .12,000 Btu/h
Heating Capacity*
. . . . . . . . . . . . . . . . . . . . . . . . . . . .14,400 Btu/h
*
Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF
(35ºC) DB, 75ºF (24ºC) WB.
(Heating at 47ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.
(For data on specific indoor units [all ducted, all non-ducted, and both ducted
and non-ducted] combinations, see the Technical and Service Manuals.)
Electrical Requirements
Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A
Voltage
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . DC 12-24V
Airflow (Lo - Med - Hi - Super Hi)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . .177 - 215 - 261 - 321 Dry CFM
170 - 207 - 252 - 309 Wet CFM
Heating . . . . . . . . . . . . . . . . . . . . . . . .184 - 201 - 219 - 335 CFM
Sound Pressure Level (Lo - Med - Hi - Super Hi)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 - 31 - 36 - 41 dB(A)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 - 31 - 36 - 41 dB(A)
DIMENSIONS
UNIT INCHES / MM
W
27-9/16 / 700
D
7-7/8 / 200
H
23-5/8 / 600
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 lbs. / 15 kg
External Finish . . . . . . . . . . . . . . . . . . . . . . . Munsell No. 1.0Y 9.2/0.2
Field Drainpipe Size O.D.. . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm
Refrigerant Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8
"
/ 9.52 mm
Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4
"
/ 6.35 mm
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
SUBMITTAL DATA: MFZ-KA12NA
. . . . . . . . 12,000 BTU/H FLOOR-STANDING INDOOR UNIT FOR MXZ-B MULTI-ZONE HEAT-PUMP SYSTEMS
Indoor Unit: MFZ-KA12NA
Wireless Remote Controller
GENERAL FEATURES
• Floor-standing unit
• Standard Hybrid Catechin Prefilter and Anti-allergy Enzyme
Filters are included with indoor unit
• Quiet operation
• Choice of fan speeds: Low, Medium, High, and Super High; Auto
fan speed control also included
• Bottom supply outlet operates in heat mode
• Wireless remote controller is included; PAR-21MAA wired
remote controller can be installed as an option
• Indoor unit powered from outdoor unit using A-Control
• Auto restart following a power outage
• Unit can be recessed mounted into wall
• Limited warranty: five years on parts and defects and seven years
on compressors
MXZ-B SERIES HEAT-PUMP OUTDOOR UNITS
SEZ-KD and PEAD-A24
MSZ-GE
MXZ-B MULTI-ZONE SYSTEMS CAN INCLUDE:
• Ducted Indoor Units:
SEZ-KD09,12,15,18NA, PEAD-A24AA
• Nonducted Indoor Units:
MSZ-GE06,09,12,15,18,24NA,
MSZ-FE09,12,18NA, MFZ-KA09,12,18NA,
PCA-A24KA, SLZ-KA09,12,15NA, and
PLA-A12,18,24BA
• A combination of both Ducted and Nonducted
Indoor Units
Refer to the separate submittal forms for the
MSZ-GE, MSZ-FE, MFZ-KA, SEZ-KD, SLZ-KA,
PEAD, PCA, PLA Indoor Units, and MXZ Outdoor
Units.
Outdoor Unit: MXZ-4B36NA
MSZ-FE
MFZ-KA
PCA-KA
SLZ-KA and PLA-ABA
OPTIONAL
A
CCESSORIES
Indoor Unit
□ Replacement Anti-allergy Enzyme Filter (MAC-415FT)
Controller Options
□ Wall-mounted Wired Remote Controller (PAR-21MAA requires
MAC-397IF)
□ MA Contact Terminal Interface (MAC-397IF)
□ M-NET Control Adapter (MAC-399IF)
□ Remote Temperature Sensor (M21-JKO-307)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)