1 SERVO PARAMETER DETAILS
1.11 Positioning extension setting servo parameters group ([Pr. PV_ _ ])
179
1
[Pr. PV07_Profile deceleration (PDEC)]
Set the deceleration used in the profile position mode (pp), profile velocity mode (pv), and JOG operation mode (jg).
The unit can be changed to 0.001 mm/s
2
, 0.0001 inch/s
2
, 0.001 degree/s
2
, or pulse/s
2
with [Pr. PT01.2 Unit for position data].
When the setting value of this servo parameter is "0", the servo motor decelerates in accordance with the time constant set in
[Pr. PT50 Speed deceleration time constant].
This function is enabled when [Pr. PT01.1] is set to "1". This function and [Pr. PT50] are mutually exclusive.
This function corresponds to [Profile deceleration (Obj. 6084h)].
When the object is mapped to the cyclic communication, do not write values with engineering tools because the controller
overwrites the servo parameter values written with engineering tools.
[Pr. PV09_Deceleration at forced stop (RSBDEC)]
Set the deceleration to be used for the forced stop deceleration function.
The unit can be changed to 0.001 mm/s
2
, 0.0001 inch/s
2
, 0.001 degree/s
2
, or pulse/s
2
with [Pr. PT01.2 Unit for position data].
When the setting value of this servo parameter is "0", the servo motor decelerates in accordance with the time constant set in
[Pr. PC24 Deceleration time constant at forced stop].
This function is enabled when [Pr. PT01.1 Speed/acceleration/deceleration unit selection] is set to "1". This function and [Pr.
PC24] are mutually exclusive.
This function corresponds to [Quick stop deceleration (Obj. 6085h)].
When the object is mapped to the cyclic communication, do not write values with engineering tools because the controller
overwrites the servo parameter values written with engineering tools.
[Pr. PV11_Homing speed extension setting (ZRFE)]
Set the servo motor speed for homing.
The unit can be changed to 0.001 mm/s, 0.0001 inch/s, 0.001 degree/s, or pulse/s with [Pr. PT01.2 Unit for position data].
This function is enabled when [Pr. PT01.1 Speed/acceleration/deceleration unit selection] is set to "1". This function and [Pr.
PT05 Homing speed] are mutually exclusive.
The setting value will be clamped at the maximum speed. When changing the speed to the permissible speed, set the speed
in [Pr. PA28.4 Speed range limit selection].
This function corresponds to [Speed during search for switch (Obj. 6099h: 01h)].
When the object is mapped to the cyclic communication, do not write values with engineering tools because the controller
overwrites the servo parameter values written with engineering tools.
Initial value
Setting range
Setting method
Ver.
0 [Refer to the text below for the unit.]
0 to 4294967295
Each axis
A5
Initial value
Setting range
Setting method
Ver.
0 [Refer to the text below for the unit.]
0 to 4294967295
Each axis
A5
Initial value
Setting range
Setting method
Ver.
500000 [Refer to the text below for
the unit.]
0 to 4294967295
Each axis
A5