134
5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
J(P)_WRITE, G(P)_WRITE
The following instruction can go in the dotted squares.
J_WRITE, JP_WRITE, G_WRITE, GP_WRITE
■
Executing condition
■
Argument
Processing details
This instruction writes data to a word device of another station.
Instruction
Executing condition
J_WRITE
G_WRITE
JP_WRITE
GP_WRITE
Input/output
argument
Name
Description
Data type
Input argument
EN
Executing condition
Bit
Jn*
Network number of the host station (1 to 239, 254)
254: Network specified in "Valid module during
other station access"
ANY16
Un*
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/
O number in three digits)
ANY16
s1
Variable that stores control data
Array of ANY16 [0..17]
s2
Start number of the host station's device that stores
write data
ANY16
s3
Start number of the target station's device to which
data are written
ANY
Output argument
ENO
Execution result
Bit
d1
Variable that turns ON upon completion of the
instruction
d2[1] also turns ON at the time of error completion.
Array of bit [0..1]
Setting
data
Internal device
R, ZR
J
\
U
\G
Zn
Constant
Others
Bit
Word
Bit
Word
(s1)
(s2)
(s3)
(d1)
CC IE F
CC IE C
NET/H
Ether
Structured ladder/FBD
EN
ENO
Jn*
d1
s1
s3
J_WRITE
EN
ENO
Un*
d1
s1
s2
s2
s3
G_WRITE
ST
J_WRITE
ENO:=
(EN, Jn*, s1, s2, s3, d1);
G_WRITE
(EN, Un*, s1, s2, s3, d1);
ENO:=