![Mitsubishi Electric MELSEC Q80BD-J71GF11-T2 User Manual Download Page 220](http://html.mh-extra.com/html/mitsubishi-electric/melsec-q80bd-j71gf11-t2/melsec-q80bd-j71gf11-t2_user-manual_238449220.webp)
218
APPX
Appendix 6 Differences in Cyclic Transmission Modes
Appendix 6
Differences in Cyclic Transmission
Modes
This section explains the differences between "Online (Normal Mode)" and "Online (High Speed Mode)" for the CC-Link IE
Field Network board. Refer to the information in this section to select "Online (Normal Mode)" and "Online (High Speed
Mode)".
Differences in performance specifications
The following items can be selected.
Differences in link scan time
The link scan times in normal mode and high speed mode are shown below when assigning 128 points to RX/RY per station,
64 points to RWw/RWr per station, and the number of connected stations is increased.
Item
Online (Normal mode)
Online (High speed mode)
Maximum number of RWw send points per local station
1024 points, 2048 bytes
256 points, 512 bytes
Maximum number of transients per link scan
4 + slave stations
×
1.5
4
Total
number of
stations
Link scan time (ms)
Total number of points
for link devices (bytes)
Online (Normal mode)
Online (High speed mode)
Network Operation Setting: "Turn
OFF or 0 Clear Input Data (RX/
RY)"
Network Operation Setting:
"Hold Input Data (RX/RY)"
2
0.75
0.24
0.23
576
4
0.85
0.33
0.29
1152
8
1.05
0.49
0.42
2304
16
1.44
0.82
0.68
4608
32
2.22
1.49
1.21
9216
64
3.78
2.82
2.26
17280
120
6.52
5.14
4.09
34560
128
112
96
80
64
48
32
16
0
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
Total number of stations
Link scan time [ms]
Normal mode
High speed mode_Input data OFF
High speed mode_Input data held
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......