![Mitsubishi Electric MELSEC iQ-R04ENCPU User Manual Download Page 292](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r04encpu/melsec-iq-r04encpu_user-manual_239140292.webp)
290
APPX
Appendix 3 Buffer Memory
RWw offset/size information
■
RWw offset/size information (Un\G19968 to Un\G20209)
The start number and the number of points of RWw for each station are stored.
The offset and size of buffer memory areas for each station number (other than a station number 0) can be calculated using
the following formulas:
• Offset buffer memory address = 19968 + (station No. - 1)
2
• Size buffer memory address = 19969 + (station No. - 1)
2
RWr offset/size information
■
RWr offset/size information (Un\G20224 to Un\G20465)
The start number and the number of points of RWr for each station are stored.
The offset and size of buffer memory areas for each station number (other than a station number 0) can be calculated using
the following formulas:
• Offset buffer memory address = 20224 + (station No. - 1)
2
• Size buffer memory address = 20225 + (station No. - 1)
2
Own station information
The information of the own station on the network is stored.
■
Own station (network card) information (Un\G20512 to Un\G20515)
■
Own station (controller) information (Un\G20520 to Un\G20536)
Address
Description
Un\G19968
Station No.1 offset
Un\G19969
Station No.1 size (in units of words)
Un\G19970
Station No.2 offset
Un\G19971
Station No.2 size (in units of words)
Un\G20206
Station No.120 offset
Un\G20207
Station No.120 size (in units of words)
Un\G20208
Station No.0 offset
Un\G20209
Station No.0 size (in units of words)
Address
Description
Un\G20224
Station No.1 offset
Un\G20225
Station No.1 size (in units of words)
Un\G20226
Station No.2 offset
Un\G20227
Station No.2 size (in units of words)
Un\G20462
Station No.120 offset
Un\G20463
Station No.120 size (in units of words)
Un\G20464
Station No.0 offset
Un\G20465
Station No.0 size (in units of words)
Address
Name
Description
Un\G20512
Manufacturer code
The master/local module information of the own station is
stored.
Un\G20513
Model type
Un\G20514
Model code
Un\G20515
Version
Address
Name
Description
Un\G20520
Controller information valid/invalid flag
Whether the value stored in the own station (controller)
information is valid or invalid is stored.
• 0: Invalid
• 1: Valid
Summary of Contents for MELSEC iQ-R04ENCPU
Page 2: ......
Page 61: ...1 FUNCTIONS 1 3 IP Packet Transfer Function 59 1 ...
Page 385: ...383 I Transient transmission 15 ...
Page 389: ......