APPX
Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions
2089
A
Batch counter (SBC)
Offset
Instruction
used
Item
Name
Recommended range
Data type
Set by
SBC
+1
Shared
among the
instructions
MODE
Control mode
0 to FFFFH
16-bit unsigned
binary
User/system
+3
ALM
Alarm detection
0 to FFFFH
16-bit unsigned
binary
User/system
+4
INH
Disable alarm detection
0 to FFFFH
16-bit unsigned
binary
User/system
+10
+11
S.PSUM
SUM1
Integrated value (integral
part)
0 to 2147483647
32-bit unsigned
binary
System
+12
+13
S.PSUM
SUM2
Integrated value
(decimal part)
0 to 2147483647
32-bit unsigned
binary
System
+14
+15
S.BC
SV1
Set value 1
0 to 2147483647
32-bit unsigned
binary
User
+16
+17
S.BC
SV2
Set value 2
0 to 2147483647
32-bit unsigned
binary
User
+26
+27
S.BC
PH
Upper limit alarm value
0 to 2147483647
32-bit unsigned
binary
User
+42
+43
S.BC
CTIM
Variation rate alarm
check time
0 to 999999 [s]
Single-precision
real number
User
+44
+45
S.BC
DPL
Variation rate alarm
value
0 to 2147483647
32-bit unsigned
binary
User
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......