1982
36 COUNTER/TIMER FUNCTION BLOCKS
36.2 Down Counter
36.2
Down Counter
CTD(_E)
These function blocks count down the number of rising edges of a signal.
Setting data
■
Description, type, data type
Processing details
■
Operation processing
1.
Counting down
• When (s1) changes from off to on, the value in (d2) is counted down by one.
• When (d2) is 0, (d1) turns on and the counting stops.
• Set the start count value to (n). When (s2) turns on, (d1) turns off and (n) is set to (d2).
2.
Start count value
The valid setting range of (n) is 0 to 32767.
Ladder, FBD/LD
Structured text
[Without EN/ENO]
[With EN/ENO]
[Without EN/ENO]
Instance name(CD:=s1,LD:=s2,PV:=n,Q:=d1,CV:=d2);
[With EN/ENO]
Instance name(EN:=en,ENO:=eno,CD:=s1,LD:=s2,PV:=n,Q:=d1,CV:=d2);
Argument
Description
Type
Data type
EN
Execution condition (TRUE: Executed, FALSE: Not executed)
Input variable
BOOL
s1(CD)
Count signal input
Input variable
BOOL
s2 (LD)
Count value set
Input variable
BOOL
n (PV)
Start count value
Input variable
INT
ENO
Output status (TRUE: Normal, FALSE: Abnormal or operation stop)
Output variable
BOOL
d1 (Q)
End of count
Output variable
BOOL
d2 (CV)
Count value
Output variable
INT
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
s1
d1
d2
s2
n
EN
ENO
d1
d2
s1
s2
n
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......