12 DATA USED FOR POSITIONING CONTROL
12.8 Control Data
467
12
12.8
Control Data
System control data
[Cd.1] Module data backup request
Set this area to write module extension parameters (positioning data and block start data) to the module extension parameter
file.
• After the data is written, 0 is automatically stored. Storing 0 indicates the completion of the writing.
• For details on the module data backup function, refer to the following.
Page 306 Module Data Backup Function
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Default value
The default value is 0.
[Cd.2] Module data initialization request
Set this area to initialize module parameters and module extension parameters (positioning data and block start data) in the
buffer memory and setting values in the module extension parameter file to their factory default settings.
• After the data is initialized, 0 is automatically stored. Storing 0 indicates the completion of the initialization.
• After the data is initialized, turn on the systm again, or reset the CPU module.
• For details on the module data initialization function, refer to the following.
Page 304 Module Data Initialization Function
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Default value
The default value is 0.
Module data backup request
Setting value
Not requested
0
Requested
1
Buffer memory name
Common for Axis 1 to 4
[Cd.1] Module data backup request
1900
Module data initialization request
Setting value
Not requested
0
Requested
1
Buffer memory name
Common for Axis 1 to 4
[Cd.2] Module data initialization request
1901
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......