11 SPECIFICATIONS OF I/O SIGNALS WITH CPU MODULE
11.3 Details of Output Signals
345
11
11.3
Details of Output Signals
The following tables shows the ON/OFF timing and conditions of the output signals.
Device No.
Signal name
Description
Y0
PLC READY
Off: PLC READY OFF
On: PLC READY ON
(a) This signal notifies the RD75 that the CPU module is normal.
• This signal is turned on and off with the program.
• This signal is turned on during the positioning control, OPR control, JOG
operation, inching operation, and manual pulse generator operation, unless
the system is in the test mode of the engineering tool.
(b) When data (including parameter) has been changed, this signal is turned off
depending on the changed item.
(c) The following processing is performed when this signal is turned off and on.
• The parameter setting range is checked.
• RD75 READY signal [X0] turns on.
(d) The following processing is performed when this signal is turned on and off.
In this case, the OFF time should be set to 100ms or more.
• RD75 READY signal [X0] turns off.
• The operating axis stops.
• M code ON signal [X4, X5, X6, X7] for each axis turns off, and 0 is stored in
[Md.25] Valid M code.
(e) When the module data backup or module data initialization is performed with
an engineering tool or the CPU module, turn off this signal.
Y4
Y5
Y6
Y7
Axis 1
Axis 2
Axis 3
Axis 4
Axis stop
Off: No axis stop request
On: Axis stop request
• When Axis stop signal is turned on, the OPR control, positioning control, JOG
operation, inching operation, and manual pulse generator operation will stop.
• By turning on this signal during the positioning operation, the operation will be
stopped.
• Whether to decelerate or suddenly stop can be selected with [Pr.39] Stop
group 3 sudden stop selection.
• During the interpolation control of the positioning operation, if this signal of
any axis is turned on, all axes in the interpolation control will decelerate and
stop.
Y8
Y9
YA
YB
YC
YD
YE
YF
Axis 1
Axis 1
Axis 2
Axis 2
Axis 3
Axis 3
Axis 4
Axis 4
Forward run
JOG start
Reverse run
JOG start
Forward run
JOG start
Reverse run
JOG start
Forward run
JOG start
Reverse run
JOG start
Forward run
JOG start
Reverse run
JOG start
Off: JOG not started
On: JOG started
• When this signal is on, the JOG operation will be performed with [Cd.17] JOG
speed. When this signal is turned off, the operation will decelerate and stop.
• When an inching movement amount is set, the specified movement amount is
output for one control cycle and the operation stops.
Y10
Y11
Y12
Y13
Axis 1
Axis 2
Axis 3
Axis 4
Positioning
start
Off: No positioning start
request
On: Positioning start
request
• The OPR operation or positioning operation is started.
• Positioning start signal is valid at the rising edge, and the operation is started.
• When this signal is turned on during BUSY, Start during operation (Warning
code: 0900H) will occur.
Y14
Y15
Y16
Y17
Axis 1
Axis 2
Axis 3
Axis 4
Execution
prohibition flag
Off: Not during execution
prohibition
On: During execution
prohibition
• If this signal is on when Positioning start signal is turned on, the positioning
control does not start until this signal is turned off. (Pulse output is not
performed.) This signal is used with Pre-reading start function.
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......