5 MANUAL CONTROL
5.2 JOG Operation
Operation example of the JOG operation
Example 1
When Stop signal is turned on during the JOG operation, the deceleration stop is executed and the JOG operation will stops.
When JOG start signal is turned on while Stop signal is turned on, Stop signal ON at start (Error code: 1908H) occurs. The
operation can be started when Stop signal is turned off and JOG start signal is off and on again.
OFF
ON
OFF
ON
OFF
ON
OFF
ON
PLC READY signal
[Y0]
RD75 READY signal
[X0]
Forward run JOG
start signal
[Y8, YA, YC, YE]
Axis stop signal
[Y4, Y5, Y6, Y7]
BUSY signal
[XC, XD, XE, XF]
Turning on of the JOG start signal
while Stop signal is on is ignored.