37 FUNCTIONS
37.16 RAS Functions
673
37
Clearing errors on the standby system CPU module from the
control system CPU module
Errors on the standby system can be cleared from the control system CPU module by using SM1679 (Error reset (the other
system)) in programs or external devices.
Error clearing procedure
Use SM1679 to clear errors.
1.
Eliminate the causes of all the continuation errors that have occurred on the standby system.
2.
Turn off and on SM1679 of the control system CPU module to clear the errors. When multiple continuation errors have
occurred, all the errors are cleared at once.
Precautions
• Error clear operation with SM1679 can be performed by the control system CPU module only. A continuation error on the
standby system CPU module cannot be cleared by turning off and on SM1679 of the standby system CPU module.
• The cause of an error which has occurred in a module other than the target CPU module for the error clear cannot be
eliminated even though the error is cleared using SM1679.
• If the error cause is not eliminated after the error clear operation, the same error is detected again.
• The error clear processing is performed in the END processing. To clear an error, execute the END instruction while
SM1679 is on.
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......