37 FUNCTIONS
37.3 Memory Copy from Control System to Standby System
Memory copy with the engineering tool
The following describes the execution procedure of memory copy using the engineering tool.
Execution procedure
1.
Connect the engineering tool to the control system CPU module.
2.
Open the "Redundant Operation" window of the engineering tool.
[Online]
[Redundant PLC Operation]
[Redundant Operation]
3.
On the control system CPU module of memory copy source, a user with the Administrator access level of the user
authentication function logs on. (Execute the memory copy only in the logged on state.)
4.
Select "Memory Copy" in the "Redundant Operation" window and click [Execute]. During the memory copy, the
MEMORY COPY LEDs of the redundant function modules in both systems flash (at 200ms intervals).
5.
When the memory copy is completed, the MEMORY COPY LED of the control system turns off and that of the standby
system turns on.
6.
Turn off and on or reset the standby system CPU module. The MEMORY COPY LED of the standby system turns off.
Control system
Standby system
Control system
Standby system
Control system
Standby system
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......