![Mitsubishi Electric MELSEC iQ-R C R12CCPU-V User Manual Download Page 150](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-c-r12ccpu-v/melsec-iq-r-c-r12ccpu-v_user-manual_239137150.webp)
148
8 MULTIPLE CPU SYSTEM FUNCTIONS
8.1 Out-of-Group I/O Fetch
8.1
Out-of-Group I/O Fetch
In a multiple CPU system, the access range of the controlled module is different from that of the non-controlled module. The
out-of-group I/O fetch function enables data which cannot be accessed to be imported. However, data cannot be imported
from the module that is an inter-module synchronization target.
Accessing controlled module
The access range to the controlled module of the CPU module is the same as that of the single CPU system. I/O refresh for
the controlled module or read from/write to the buffer memory of an intelligent function module is enabled.
Accessing non-controlled module
Access to the non-controlled module of the CPU module is limited to reading the buffer memory of the intelligent function
module. However, the ON/OFF data of output (Y) of the non-controlled module can be imported by "I/O Setting Outside
Group".
: Accessible,
: Not accessible
I/O Setting Outside Group
Set the I/O state outside the group.
[System Parameter]
[Multiple CPU Setting]
[Other PLC Control Module Setting]
[I/O Setting Outside Group]
Window
Displayed items
Access target
Accessibility
When "Import" is selected in "I/O
Setting Outside Group"
When "Not Imported" is selected
in "I/O Setting Outside Group"
Input (X)
Read data from
another CPU
module
Output (Y)
Write data to
another CPU
module
(Non-processing)
Read data from
another CPU
module
(Non-processing)
Buffer memory of an intelligent function module
Read data
Write data
(Error)
(Error)
Item
Description
Setting range
Default
Input Status Outside Group
Set the input state outside the group.
• Not Imported
• Import
Not Imported
Output Status Outside
Group
Set the output state outside the group.
• Not Imported
• Import
Not Imported
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......