![Mitsubishi Electric MELSEC FX3G Programming Manual Download Page 153](http://html.mh-extra.com/html/mitsubishi-electric/melsec-fx3g/melsec-fx3g_programming-manual_239083153.webp)
151
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.11 Index Register [V and Z]
1
Int
roduct
ion
2
O
ver
view
3
In
str
uc
tion
Li
st
4
D
evices
in D
etail
5
Spec
ified t
he
D
evice &
C
onst
ant
6
Bef
ore
Pr
ogr
am
m
ing
7
B
asic
In
st
ru
ct
io
n
8
FN
C
00-FN
C
09
P
rogr
am
F
low
9
FN
C
10
-FN
C
19
Mo
ve
&
Co
mp
are
10
FNC2
0-F
NC2
9
Ar
ith.
&
Logic
O
per
ation
4.11.3 Indexing of devices
Available devices and the contents of indexing are as described below:
→
For indexing method and cautions, refer to Section 5.7.
Decimal devices/numeric values: M, S, T, C, D, R, KnM, KnS, P and K
For example, when "V0 = K5" is specified and "D20V0" is executed, an instruction is executed for the device
number D25 (D20 + 5).
Constants can be indexed also. When "K30V0" is specified, an instruction is executed for decimal value K35
(30 + 5).
Octal devices: X, Y, KnX and KnY
For example, when "Z1 = K8" is specified and "X0Z1" is executed, an instruction is executed for the device
number X10 (X0 + 8: addition of octal value). When indexing for a device whose device number is handled in
octal, a numeric value converted into octal is added for the contents of V and Z.
Accordingly, note that when "Z1 = K10" is specified "X0Z1" indicates that X12 is specified, and X10 is not
specified.
Hexadecimal numeric values: H
For example, when "V5 = K30" is specified and a constant "H30V5" is specified, it is handled as H4E (30H +
K30). When "V5 = H30" is specified and a constant "H30V5" is specified, it is handled as H60 (30H + 30H).