![Mitsubishi Electric MELSEC FX2N-2LC User Manual Download Page 70](http://html.mh-extra.com/html/mitsubishi-electric/melsec-fx2n-2lc/melsec-fx2n-2lc_user-manual_239074070.webp)
FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-16
7.2.26
BFM #43 (CH1) and BFM #62 (CH2): Primary delay digital filter setting
In BFM #43, set the primary delay digital filter of CH1. In BFM #62, set the primary delay digi-
tal filter of CH2.
The FX
2N
-2LC is equipped with the software input filter so that fluctuation of the measured
value (PV) caused by noise can be reduced. The time constant of this input filter can be set in
accordance with the characteristics of the control target and the noise level.
If the time constant is too small, the input filter cannot give required effect. If the time constant
is too large, the input responsibility is deteriorated.
The allowable set range is from 0 to 100 sec. When BFM #43/#62 is set to "0", the filter func-
tion is disabled.
While the filter function is disabled, data is acquired in the sampling cycle (500 ms).
Input of actual measured value (PV)
Input of measured value (PV) processed
by the primary delay digital filter
Amplitude
processed by
the filter
Input amplitude
Pulse input caused by noise
Summary of Contents for MELSEC FX2N-2LC
Page 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Page 4: ...FX2N 2LC Tempereture Control Block ii ...
Page 6: ...FX2N 2LC Tempereture Control Block iv ...
Page 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Page 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Page 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Page 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Page 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Page 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Page 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Page 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Page 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Page 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Page 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Page 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Page 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Page 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...