3. Setting
29
3.5. Setting Menu 2: Communication Settings (Setting the MODBUS
®
TCP communication)
<Setting flow when with ME-0000MT-SS96>
In the operation mode, press
+
simultaneously for 2 seconds or more, and the following operation
becomes available.
SET
RESET
Set the subnet mask.
Select the subnet mask from the below table.
(1)
128.0.0.0
(9)
255.128.0.0
(17)
255.255.128.0
(25)
255.255.255.128
(2)
192.0.0.0
(10)
255.192.0.0
(18)
255.255.192.0
(26)
255.255.255.192
(3)
224.0.0.0
(11)
255.224.0.0
(19)
255.255.224.0
(27)
255.255.255.224
(4)
240.0.0.0
(12)
255.240.0.0
(20)
255.255.240.0
(28)
255.255.255.240
(5)
248.0.0.0
(13)
255.248.0.0
(21)
255.255.248.0
(29)
255.255.255.248
(6)
252.0.0.0
(14)
255.252.0.0
(22)
255.255.252.0
(30)
255.255.255.252
(7)
254.0.0.0
(15)
255.254.0.0
(23)
255.255.254.0
(8)
255.0.0.0
(16)
255.255.0.0
(24)
255.255.255.0
③
MODBUS
®
TCP
Subnet mask
Set the local station IP address for MODBUS
®
TCP by each octet.
000.000.000.000 to 192.168.3.10 to 255.255.255.255
②
MODBUS
®
TCP
IP address
* If invalid IP address is set, error code E05 is appears.
If that happens, press and set again after review
the IP address.
[Range of configurable IP address]
1.0.0.0 to 126.255.255.255
128.0.0.0 to 191.255.255.255
192.0.0.0 to 223.255.255.255
The following IP addresses cannot be configured.
・
0.0.0.0
・
xxx.xxx.xxx.255 (xxx are any values)
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
Set the setting menu number to “2”.
(as shown in the right figure)
Setting Menu
SET
Select either of “MODBUS
®
TCP communication” or “MODBUS
®
RTU communication.”
Mb. tcP
Mb.rtu
(MODBUS®TCP communication)
(MODBUS
®
RTU communication)
When “MODBUS® RTU communication” is selected,
refer to
①
MODBUS®RTU Address at page 26.
Hereafter, MODBUS®TCP communication setting describes.
①
Communication
setting selection