3. Setting
28
3.9.
Setting Menu
8:
Special Settings (Setting Operation Time, Phase Display, IEC Mode)
Set the operation time, phase display, IEC mode.
In the operation mode, press
and
simultaneously for 2 seconds or more, and the following operation becomes
available.
For more details abo
ut each function, refer to the corresponding pages.
Operation time
⇒
page 45
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
RESET
Set the target for counting Operation time threshold.
When the auxiliary power (AUX) is selected for the Operation time,
this display will be skipped.
(
1
)
When current is set target for counting Operation time.
*:If
“
min
”
is selected, the Operation time will be counting when
display of current is not 0A.
(
2
)
When voltage is set target for counting Operation time.
*:If
“
min
”
is selected, the Operation time will be counting when
display of voltage is not 0V.
③
Operation time
threshold
min
1 to 120%
(
Setting step 1%
)
min
20 to 120%
(
Setting step 1%
)
Set the setting menu number to “8”.
(as shown in the right figure)
Setting menu
Set
“on or off” of the Operation time display that integrates
the time while the target for counting is input and display
it as the load Operation time.
①
Operation time
display
oFF
on
(
Not displayed
)
(
Displayed
)
Select the target for counting Operation time from
the auxiliary power, current, and voltage.
Item
3-phase 4-wire
1-phase 2-wire
Others
AUX
AUX
AUX
AUX
A
A
AVG
A
A
AVG
V
V
AVG
(
L-N
)
V
V
AVG
(
L-L
)
②
Target for counting
Operation time
setting
(
Auxiliary power
)
(
Current
)
(
Voltage
)
AUX
A
V