6 N:N NETWORK
6.3 Communication Setting
97
6
Request code
The numerical value of each parameter corresponding to the request code is treated as real number data without a decimal
point.
In addition, the minimum and maximum values are determined for LE7-40GU, and when a value exceeding this data is
written, it is automatically rewritten to the minimum or maximum value.
In this case, an "Out of data range" alarm is generated.
Request
code
Name
Monitor/
settings
Extension
option
Minimum value
Maximum value
Unit
H000(0)
H001(1)
Total tension
Monitor
0 or less
2000 or more
N/
10 N
H002(2)
Left tension
Monitor
0 or less
2000 or more
N/
10 N
H003(3)
Right tension
Monitor
0 or less
2000 or more
N/
10 N
H004(4)
Left input voltage
Monitor
-1500 or less
1500 or more
mV
H005(5)
Right input voltage
Monitor
-1500 or less
1500 or more
mV
H006(6)
H007(7)
H008(8)
H009(9)
H00A(10)
H00B(11)
H00C(12)
H00D(13)
H00E(14)
H00F(15)
H010(16)
Tension upper limit detection
Setting
0
Tension full scale
N/
10 N
H011(17)
Tension lower limit detection
Setting
0
Tension full scale
N/
10 N
H012(18)
Detection outside target tension range
Setting
0
50
%
H013(19)
Tension display filter
Setting
5
80
sec
H014(20)
Tension detection filter
Setting
0
80
sec
H015(21)
Tension output filter
Setting
0
80
sec
H016(22)
H017(23)
H018(24)
H019(25)
H01A(26)
H01B(27)
H01C(28)
H01D(29)
H01E(30)
H01F(31)
H020(32)
Sensor input type selection
Setting
0 (LX type), 1 (strain gauge)
H021(33)
Tension full scale
Setting
1
2000
N/
10 N
H022(34)
Tension display decimal point selection
Setting
0 (1), 1 (0.1), 2 (0.01)
H023(35)
Tension display unit selection
Setting
0 (N), 1 (
10 N)
H024(36)
Span target tension
Setting
1
Tension full scale
N/
10 N
H025(37)
Left manual zero calibration
Setting
-999
999
N/
10 N
H026(38)
Right manual zero calibration
Setting
-999
999
N/
10 N
H027(39)
Left manual span calibration
Setting
50
300
%
H028(40)
Right manual span calibration
Setting
50
300
%
H029(41)
H02A(42)
H02B(43)
Summary of Contents for LE7-40GU
Page 1: ...LE7 40GU INSTRUCTION MANUAL Communication ...
Page 2: ......
Page 10: ...8 TRADEMARKS 150 ...
Page 11: ...9 CONTENTS ...
Page 37: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 35 3 ...
Page 38: ...36 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Page 39: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 37 3 ...
Page 40: ...38 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Page 57: ...4 SLMP COMMUNICATION 4 3 Reference Program 55 4 Program example ...
Page 58: ...56 4 SLMP COMMUNICATION 4 3 Reference Program ...
Page 59: ...4 SLMP COMMUNICATION 4 3 Reference Program 57 4 ...
Page 60: ...58 4 SLMP COMMUNICATION 4 3 Reference Program ...
Page 61: ...4 SLMP COMMUNICATION 4 3 Reference Program 59 4 ...
Page 82: ...80 5 MODBUS TCP SLAVE 5 3 Reference Program Program example ...
Page 83: ...5 MODBUS TCP SLAVE 5 3 Reference Program 81 5 ...
Page 84: ...82 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Page 85: ...5 MODBUS TCP SLAVE 5 3 Reference Program 83 5 ...
Page 86: ...84 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Page 110: ...108 6 N N NETWORK 6 4 Reference Program Program example ...
Page 111: ...6 N N NETWORK 6 4 Reference Program 109 6 ...
Page 112: ...110 6 N N NETWORK 6 4 Reference Program ...
Page 147: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 145 7 Function code H03 Read holding register ...
Page 149: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 147 7 ...
Page 153: ......