System primary circuit antifreeze
paragraph.
4.13.4
ROOM TEMPERATURE ANTIFREEZE (ONLY WITH ZONES ACTIVE)
Protection is related to the value read by the room air temperature probe N-THC.
The involved resources are the compressor (J10) and the delivery heater (NO8)
The purpose of this function is to protect the internal ambient from excessive cold. When active, it uses the available resources as configured for
normal system heating (HP, delivery heater, alternative heat source), based on the function described below:
Enabled
OFF
HP
Room air T [°C]
Room antifreeze setpoint
(0140)
Room antifreeze disable
hysteresis (011E, 011F)
The Heat Pump will work based on the set antifreeze setpoint (default = 5°C); if inhibited (for the details refer to the "Replacement heater
” and
” paragraphs), the other available resources will be act
ivated.
For the default values of the various parameters, see the parameters table