background image

This manual confers no industrial property rights or any rights of any other kind, 
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be 
held responsible for any problems involving industrial property rights which may 
occur as a result of using the contents noted in this manual.

Warranty

Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for 

accidents, and compensation for damages to products other than Mitsubishi products.

(4) Replacement by the user, maintenance of on-site equipment, start-up test run 

and other tasks.

For safe use

This product has been manufactured as a general-purpose part for general 
industries, and has not been designed or manufactured to be incorporated in 
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric 
power, aerospace, medicine or passenger movement vehicles, consult with 
Mitsubishi Electric.
This product has been manufactured under strict quality control. However 
when installing the product where major accidents or losses could occur if the 
product fails, install appropriate backup or failsafe functions in the system.

HEAD OFFICE  : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Side

A

Side

B

JAPANESE

ENGLISH

JY997D22501F

Side

B

Safety Precautions

 

(Read these precautions before use.)

If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
This manual classifies the safety precautions into two categories: 

 and 

.

Depending on the circumstances, procedures indicated by 

 may also

cause severe injury.

It is important to follow all precautions for personal safety.

Associated Manuals

How to obtain manuals

For the necessary product manuals or documents, consult with the Mitsubishi
Electric dealer from where you purchase your product.

Certification of UL, cUL standards

FX

3U

-1PSU-5V units comply with the UL standards (UL, cUL)

UL, cUL registration number: E95239

Regarding the standards that comply with the main unit, please refer to either the
FX series product catalog or consult with your nearest Mitsubishi product provider.

Compliance with EC directive (CE Marking)

This product complies with EC directive, however, this document does not
guarantee that a mechanical system including this product will comply with EC
directive.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more information please
consult with your nearest Mitsubishi product provider. 
Regarding the standards that comply with the main unit, please refer to either the
FX series product catalog or consult with your nearest Mitsubishi product provider.

Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.

Manual name

Manual No.

Description

FX

3G

 Series 

User’s Manual 
- Hardware Edition

JY997D31301

MODEL CODE: 

09R521

Explains FX

3G

 Series PLC 

specification details for I/O, wiring, 
installation, and maintenance.

FX

3U

 Series 

User’s Manual 
- Hardware Edition

JY997D16501

MODEL CODE: 

09R516

Explains FX

3U

 Series PLC 

specification details for I/O, wiring, 

installation, and maintenance.

MELSEC iQ-F FX5U
User's Manual
(Hardware)

JY997D55301

MODEL CODE:

09R536

Explains the FX5U PLC 

specifications for I/O, wiring,

installation, and maintenance.

Caution for compliance with EC Directive

Please use the FX

3U

-1PSU-5V while installed in conductive shielded control panels

under a general industrial environment.

Programmable controllers are open-type devices that must be installed and used
within conductive control panels. Please secure the control box lid to the control box
(for conduction). Installation within a control box greatly affects the safety of the
system and aids in shielding noise from the programmable controller.

For the control panel, use the product having sufficient strength, fire protectiveness

and shielding property to an installation environment.

Caution for compliance with the LVD directive (EN61010-2-201:2013)

*1

To an external connection port other than AC power supply terminal and AC input/

output terminal, connect the circuit separated from a dangerous voltage by a
double/reinforced insulation.

Do not wire two or more crimp terminals to one terminal. (If the wiring with two or
more wires is needed, take an appropriate action such as adding an external
terminal.)

For crimp terminals to be used for the wiring applied with 30V AC or higher, use the

products with insulating sleeves.

Cutoff device such as a breaker or a circuit protector should be installed in
accordance with the following precautions.

- Use EN60947-1 or EN60947-3 standards.
- Place the cutoff device so that it can be operated easily.
- Specify that the cutoff device is for this equipment.

*1 For the time of compliance with the LVD directive (EN61010-2-201:2013), refer

to the manual of the PLC to be connected.

1. Introduction

When the FX

3G, 

FX

3U

 internal power supplied from the FX

3G, 

FX

3U

, FX5U PLC (AC

power supply type) is insufficient for powering the output extension blocks or special
function blocks, the FX

3U

-1PSU-5V (extension power supply unit) is available. Up to

two FX

3U

-1PSU-5V units may be connected to a FX

3U

, FX5U PLC system. Only one

FX

3U

-1PSU-5V unit may be connected to a FX

3G

 PLC system. Connect extension

equipment to the FX

3U

-1PSU-5V according to the configuration specification limits

described in the following manuals.
For details on installation and wiring, and system configuration including the FX

3U

-

1PSU-5V, refer to the following manuals.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

1.1 Incorporated Items

Check that the following product and items are included in the package:

1.2 External Dimensions and Part Names

Product

FX

3U

-1PSU-5V extension power supply unit

Accessories

Dust proof protection sheet
Extension cable

Installation manual (This manual)

Terminal

  layout

Unit: mm (inches)
MASS (Weight): Approx. 0.3kg (0.66 lbs)

3)

4)

5)

9(0.36")

87(3.43")

90(3.55")

80(3.15")(Mounting hole pich)

55(2.17")

4

(0.16")

1)

2)

2-

φ

4.5 Mounting hole

7)

6)

8)

      Top cover is removed

*1

is a mark that instructs to use the cable with an appropriate temperature

rating (80

°

C or more) for wiring.

2. Installation  

2.1 Arrangements

The product connects on the right side of an PLC main unit, input/output 
extension unit/block or special function unit/block.
For further information of installation arrangements, refer to the following manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

2.2 Mounting

The product is mounted by the following method.

Direct mounting

DIN rail mounting

2.2.1

Direct Mounting

The product can be mounted with M4 screws by using the direct mounting holes. 
Refer to the External Dimensions (section 1.2) for the product’s mounting hole pitch
information.
An internal space between each unit of 1 to 2 mm (0.04" to 0.08") is necessary.
For further information on direct installation, also refer to the following manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

1)

2)

3)

4)

5)

6)
7)

8)

POWER LED (green)

Direct mounting hole:2 holes of 

φ

4.5 (0.18") (mounting screw: M4 screw)

Name plate

*1

DIN rail mounting groove (DIN rail: DIN46277)

DIN rail mounting hook
Extension connector for preceding unit/block

Power supply terminal block

 shows a function grounding terminal.

Extension connector for next unit/block

INSTALLATION 
PRECAUTIONS

Cut off all phases of the power source externally before starting the installation

work, thus avoiding electric shock or damages to the product.

INSTALLATION 
PRECAUTIONS

Use the product in the environment within the general specifications described in

the PLC main unit manual (Hardware Edition). Never use the product in areas with

dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl

2

, H

2

S, SO

2

, or NO

2

),

flammable gas, vibrations or impacts, or expose it to high temperature,

condensation, or wind and rain. If the product is used in such a place described

above, electrical shock, fire, malfunction, damage, or deterioration may be caused.

Do not touch the conductive parts of the product directly. 

Doing so may cause device failures or malfunctions.

Install the product securely using the DIN rail or screws.

Install the product on a flat surface. If the mounting surface is rough, undue force

will be applied to the PC board, thereby causing nonconformity.

When drilling screw holes or wiring, make sure that cutting and wiring debris do

not enter the ventilation slits of the PLC.

Failure to do so may cause fire, equipment failures or malfunctions.

Be sure to remove the dust proof sheet from the PLC's ventilation slits when

installation work is completed.

Failure to do so could cause fires, equipment failures, and malfunctions.

Fit the extension cables and communication cables securely to the designated

connectors. Contact failures may cause malfunctions.

Notes

When a dust proof sheet is supplied with an unit, keep the sheet applied to the

ventilation slits during installation and wiring work.

To prevent temperature rise, do not install the PLC on a floor, a ceiling or a vertical

surface. Install it horizontally on a wall.

Keep a space of 50mm (1.97”) or more between the unit main body and another

device or structure. Install the unit as far away as possible from high-voltage lines,

high-voltage devices and power equipment.

Failure to do so may cause fire, equipment failures or malfunctions.

2.2.2

DIN Rail Mounting

The product can be mounted on a DIN rail (DIN46227, 35mm width).

1) Connect the extension cable (right fig. A)

to the main unit, input/output extension
unit/block and special function unit/block
on the left.
For details on the extension cable 
connection, refer to the following manual.

→ 

FX

3G

 Series User's Manual

- Hardware Edition

→ 

FX

3U

 Series User's Manual

- Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual

(Hardware)

2) Fit the upper edge of the DIN rail mounting

groove (right fig. B) onto the DIN rail.

3) Press the product against the DIN rail.

4) Connect the extension cable (right figure

A) connected in the procedure 1) to FX

3U

-

1PSU-5V.
For details on the extension cable 
connection, refer to the following manual.

→ 

FX

3G

 Series User's Manual

- Hardware Edition

→ 

FX

3U

 Series User's Manual

- Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual

(Hardware)

3. Wiring  

WIRING PRECAUTIONS

Connect the AC power supply wiring to the dedicated terminals described in

this manual. If an AC power supply is connected to a DC input/output terminal
or DC power supply terminal, the PLC will be burnt out.

Cut off all phases of the power source externally before starting the wiring

work, thus avoiding electric shock or damages to the product.

Ensure the top cover is attached to the product before turning on the power or
starting the operation after wiring work.
Failure to do so may cause electric shock.

The temperature rating of the cable should be 80

°

C or more.

WIRING PRECAUTIONS

Perform class D grounding (grounding resistance: 100

  or  less)  to  the

grounding terminal in the main unit and extension units with a 2mm2 or
thicker wire. Do not connect the grounding terminal at the same point as a
heavy electrical system (refer to section 3.3).

When drilling screw holes or wiring, cutting chips or wire chips should not
enter ventilation slits. This may cause fire, failures, or malfunctions.

Properly perform wiring to the terminal block in accordance with the following
precautions. Failure to do so may cause electric shock, equipment failures, a
short-circuit, wire breakage, malfunctions, or damage to the product.

- Termination of the wire should follow the dimensions described in the manual.
- Tightening torque should the specifications in the manual.

A

Main unit, 

input/output 

extension 

unit/block or 

special function 

unit/block

2)

3)

B

A

FX

3U

-1PSU-5V

3.1 Applicable Cable and Terminal Tightening Torque

The size of the terminal screws is M3.
The end disposal of the cable shows below.
Tighten the terminal to a torque of 0.5N

m to 0.8N

m. Do not tighten terminal

screws exceeding the specified torque.
Failure to do so may cause equipment failures or malfunctions.

When one wire is connected to one terminal

<Reference>

When two wires are connected to one terminal

*1

<Reference>

*1 To adapt the LVD directive (EN61010-2-201:2013) of the EC directive, avoid

the wiring with two wires to the built-in terminal, and take an appropriate
action such as adding an external terminal.
For the time of compliance with the LVD directive (EN61010-2-201:2013),
refer to the manual of the PLC to be connected.

3.2 Power Supply Wiring

For the power supply wiring, refer to the following manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

Note;

The FX

3U

-1PSU-5V power supply should be turn ON simultaneously or

before the PLC main unit. Before turning the power OFF, ensure the
safety of the system and then simultaneously turn the main unit, FX

3U

-

1PSU-5V, and other extension equipment (the special extension
equipment is included) OFF.
For details, refer to the following PLC manual

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

Grounding and power cables should be positioned to exit the unit from
above as shown in the following figure.

When connecting an input (only) extension block and an input/output
extension block (e.g. FX

2N

-8ER) to the FX

3U

-1PSU-5V, supply the

power of input circuit for them from the 24V DC service power supply of
the nearest preceding main unit or powered extension unit.
For details, refer to the following PLC manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

Terminal 

manufacturer

Type No.

Applicable 

cable

Certification

Pressure 

bonding tool

J.S.T. Mfg. Co.,
Ltd.

FV1.25-B3A AWG22 to 16

UL Listed

YA-1 (J.S.T. 
Mfg. Co., Ltd.)

FV2-MS3

AWG16 to 14

Terminal 

manufacturer

Type No.

Applicable 

cable

Certification

Pressure 

bonding tool

J.S.T. Mfg. Co.,
Ltd.

FV1.25-B3A AWG22 to 16

UL Listed

YA-1 (J.S.T. 
Mfg. Co., Ltd.)

’[Žq

Terminal

Terminal

screw

Crimp

terminal

6.2mm(0.24")

or less

φ

3.2 (0.13")

φ

3.2 (0.13")

6.2mm(0.24")

or less

Terminal

Terminal

screw

Crimp

terminal

6.3mm(0.25")

or more

φ

3.2 (0.13")

φ

3.2 (0.13")

6.2mm(0.24")

or less

6.2mm(0.24")

or less

6.3mm(0.25")

or more

Grounding cable and power cable

Power supply wiring

3.3 Grounding

Grounding should be performed as stated below.

The grounding resistance should be 100

 or less.

Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
For details, refer to the following manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

Use ground wires thicker than AWG14 (2 mm

2

).

The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.

4. Specification

 

  

DESIGN
PRECAUTIONS

Provide a safety circuit on the outside of the PLC so that the whole system
operates to ensure the safety even when external power supply trouble or PLC
failure occurs.
Otherwise, malfunctions or output failures may result in an accident.
1) An emergency stop circuit, a protection circuit, an interlock circuit for opposite

movements, such as normal and reverse rotations, and an interlock circuit for
preventing damage to the machine at the upper and lower positioning limits
should be configured on the outside of the PLC.

2) When the PLC CPU detects an error, such as a watch dog timer error, during

self-diagnosis, all outputs are turned off. When an error that cannot be
detected by the PLC CPU occurs in an input/output control block, output con-
trol may be disabled.
Design external circuits and mechanisms to ensure safe operations of the
machine in such a case.

3) When some sort of error occurs in a relay, triac or transistor of the output unit/

block, output may be kept on or off.
For output signals that may lead to serious accidents, design external circuits
and mechanisms to ensure safe operations of the machine.

DESIGN
PRECAUTIONS

Make sure to observe the precautions below in order to prevent any damage to a
machine or any wires accident which might be caused by abnormal data written in
the PLC due to the influence of noise:
1) Do not lay close or bundle the control line with the main circuit, high-voltage

power line, or load line. 
Otherwise effects of noise or surge induction are likely to take place.
Keep a safe distance of more than 100 mm (3.94") from the above when wiring.

2) Ground the shield wire or shield of a shielded cable at one point on the PLC.

However, do not ground at the same point as high voltage lines.

STARTUP AND 
MAINTENANCE 
PRECAUTIONS

Do not disassemble or modify the PLC.
Doing so may cause failure, malfunction or fire.
* For repair, contact your local Mitsubishi Electric representative.

Do not drop the product or do not exert strong impact, doing so may cause
damage.

Do not use the chemicals for cleaning.

If there is the possibility of touching the PLC inside a control panel in
maintenance, make sure to discharge to avoid the influence of static electricity.

DISPOSAL 
PRECAUTIONS

Please contact a company certified in the disposal of electronic waste for

environmentally safe recycling and disposal of the product.

FX

3U

-1PSU-5V

L

N

100-240V AC

Grounding

(Grounding resistance: 100

 or less)

PLC

Another

equipment

PLC

Another

equipment

PLC

Another

equipment

Shared grounding

Good condition

Common grounding

Not allowed

Independent grounding

Best condition

4.1 Applicable PLC

The version number can be checked by monitoring D8001 as the last three digits
indicate it.

*1 An FX5-CNV-BUS or FX5-CNV-BUSC is necessary to connect the FX

3U

-1PSU-

5V with the FX5U PLC.

4.2 General Specifications

The items other than the following are equivalent to those of the PLC main unit.
For the general specification, refer to the following manual. 

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

4.3 Power Supply Specifications

*1

The output current is proportional to the ambient temperature as 
shown by the derating curve below.
FX

3U

-1PSU-5V should be used in the range of the output current according

to this derating curve.

Note for system configuration

For further details on system configuration, refer to the following manual.

→ 

FX

3G

 Series User's Manual - Hardware Edition

→ 

FX

3U

 Series User's Manual - Hardware Edition

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

When connected to the FX3U/FX3G PLC

TRANSPORT AND 
STORAGE PRECAUTIONS

The product is a precision instrument. During transportation, avoid impacts larger

than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the

product. After transportation, verify operation of the product and check for
damage of the mounting part, etc.

Model name

Applicability

FX

3U

 Series PLC

From the first product

FX

3G

 Series PLC

From the first product

FX5U PLC

*1

From the first product

Items

Specifications

Supply voltage

100 to 240V AC

Voltage fluctuation range

-15%, +10%

Rated frequency

50/60Hz

Allowable momentary 
power failure time

The allowable momentary power failure time
depends on the power supply used.

100V AC power supply system:
The operation is continued to the momentary 
power failure for 10 or less ms.

200V AC power supply system:
The operation is continued to the momentary 
power failure for 100 or less ms.

In-rush current

30A Max. 5 ms or less/100V AC
65A Max. 5 ms or less/200V AC

Power consumption

20W Max.

Output current
(Internal for 
supply)

24V DC

300mA

*1

5V DC

1000mA

*1

1000

800

Ambient temperature [

°

C]

55

40

300
200

5V DC

Output current [mA]

24V DC

0

Up to two FX

3U

-1PSU-5V units may be connected to a FX

3U

 PLC

system.
Only one FX

3U

-1PSU-5V unit may be connected to a FX

3G

 PLC

system.

The total of the number of I/O occupied points of the input/output
extension block connected to FX

3U

-1PSU-5V should be the 32 or less

points.

The total of the consumed current of the extension equipment 
connected to FX

3U

-1PSU-5V should be the output current capacity or

less.
However, when connecting an input (only) extension block and an input/
output extension block (e.g. FX

2N

-8ER) to the FX

3U

-1PSU-5V, supply

the power of input circuit for them from the 24V DC service power
supply of the nearest preceding main unit or powered extension unit.

Do not use FX

3U

-1PSU-5V combining the DC-power-supply type main

unit.

Up to one extension cable (FX

0N

-65EC, FX

0N

-30EC) may be 

connected in one system.

When connected to the FX5U PLC

Refer to the following manual.

→ 

MELSEC iQ-F FX5U User's Manual (Hardware)

Note: This symbol mark is for China only.

含有有害6物质的名称,含有量,含有部品

 本产品中所含有的有害6 物质的名称,含有量,含有部品如下表

所示。

产品中有害物质的名称及含量

本表格依据SJ/T 11364的规定编制。

○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572

 规定的限量要求以下。 

×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T 
    26572规定的限量要求。

部件名称

有害物质

(Pb)

(Hg)

(Cd)

六价铬

(Cr(VI))

多溴联苯

(PBB)

多溴

二苯醚
(PBDE)

可编程
控制器

外壳

印刷基板

×

「电器电子产品有害物质限制使用标识要求」的表示方式

FX

3U

-1PSU-5V

INSTALLATION MANUAL

This manual describes the part names, dimensions, installation, wiring and
specifications of the product. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration
The company name and the product name to be described in this manual are the
registered trademarks or trademarks of each company.

Effective December 2017
Specifications are subject to change without notice.

©

 2006 Mitsubishi Electric Corporation

Manual Number

JY997D22501

Revision

F

Date

December 2017