Copying and verifying parameters on the operation panel
Parameters
5 - 572
5.15.2 Parameter
verification
Whether the parameter settings of inverters are the same or not can be checked.
NOTES
●
"
" appears... Why?
Parameter write error. Perform the operation from step
again.
●
"
" and "
" are displayed alternately.
Appears when parameter copy is performed between inverters FR-F820-02330(55K) or lower
or inverters FR-F840-01160(55K) or lower and inverters FR-F820-03160(75K) or higher or FR-
F840-01800(75K) or higher.
When CP and 0.00 flicker alternately, set the Pr. 989 "Parameter copy alarm release" as shown
below (initial value):
After setting Pr. 989, perform setting of Pr. 9, Pr. 30, Pr. 51, Pr. 56, Pr. 57, Pr. 72, Pr. 80, Pr. 82, Pr.
90 to Pr. 94, Pr. 453, Pr. 455, Pr. 458 to Pr. 462, Pr. 557, Pr. 859, Pr. 860, and Pr. 893 again.
Operation
Copy the parameter settings of the verification source inverter to operation panel according to the procedure on page
5-571.
Move the operation panel to the inverter to be verified.
Screen at power-ON
The monitor display appears.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
!
Selecting the parameter number
Turn
to "
" (parameter copy). Press
. "
" appears.
Parameter verification
Turn
to change to setting value "
" (parameter copy verification mode).
Press
. Verification of the parameter settings copied to the operation panel and the parameter settings of the
verification destination inverter is started. (It takes about 60 seconds to verify all the settings. During verification,
"
" flickers.)
If there are different parameters, the different parameter number and "
" flicker.
To continue verification, press
.
$
"
" and "
" flicker alternately after verification ends.
Tab. 5-294:
Parameter verification
NOTE
"
" flickers... Why?
The set frequency may be incorrect. To continue verification, press SET key.
Pr. 989 setting Operation
10
Cancels the alarm of FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
100
Cancels the alarm of FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......